OPERATION
MODE Button
During normal operations the mode button is used to display the accumulated
hours and hydraulic oil temperature if this option is installed.
The first time the
MODE
button is pressed, the FROG-D 3P will display the
generator hours.
Generator Operating Time is:
50 hours
Over Current Warning
When the generator is operating outside the range of its rated capacity, the current
display will start to flash. When line 4, 5, or 6 is selected, the display will flash ‘
OC
’ to
indicate Over Capacity since no current draw reading is display when line 4, 5, or 6
are selected. An optional audible buzzer can also be connected for audio warning.
Voltage Out-Of-Range Warning
If the output voltage is below 200 VAC or above 270 VAC, the VOLTS readout
will begin to flash. This will give the operator an indication that the generator output
falls outside the safe operating level. There is no audible alarm for the voltage out of
range warning.
Hydraulic Oil Temperature (Optional )
This warning will be activated if the oil temperature rises above 180 deg. F. The
frequency readout will flash “OIL“ to warn the operator and the optional audio alarm
will also be activated.
Pressing the
MODE
button again will switch the display to show the engine oil
temperature.
Hydraulic Oil Temperature is:
150 degrees F
Pressing the
MODE
button again will return the display to normal operations.