OPERATION

MODE Button

During normal operations the mode button is used to display the accumulated 

hours and hydraulic oil temperature if this option is installed.

The first time the 

MODE

 button is pressed, the FROG-D 3P will display the 

generator hours. 

Generator Operating Time is:

50 hours

Over Current Warning

When the generator is operating outside the range of its rated capacity, the current 

display will start to flash. When line 4, 5, or 6 is selected, the display will flash ‘

OC

’ to 

indicate Over Capacity since no current draw reading is display when line 4, 5, or 6 

are selected. An optional audible buzzer can also be connected for audio warning.

Voltage Out-Of-Range Warning

If the output voltage is below 200 VAC or above 270 VAC, the VOLTS readout 

will begin to flash. This will give the operator an indication that the generator output 

falls outside the safe operating level. There is no audible alarm for the voltage out of 

range warning.

Hydraulic Oil Temperature (Optional )

This warning will be activated if the oil temperature rises above 180 deg. F. The 

frequency readout will flash “OIL“ to warn the operator and the optional audio alarm 

will also be activated.

Pressing the 

MODE

 button again will switch the display to show the engine oil 

temperature.

Hydraulic Oil Temperature is:

150 degrees F

Pressing the 

MODE

 button again will return the display to normal operations.

Summary of Contents for FDA300

Page 1: ...arch com 26 Southern Blvd Nesconset NY11767 TEL 631 724 8888 FAX 631 360 9727 TOLL FREE 1 800 645 0074 FROG D 3P THREE PHASE GENERATOR DISPLAY FREQUENCY READOUT OF GENERATOR MODEL FDA300 Document Numb...

Page 2: ...ransformer 9 Install Optional Hydraulic Oil Temperature Sensor 9 Install Optional Buzzer 9 OPERATION 10 WIRING 12 Star Winding Connections 14 Delta Winding Connections 15 List of Figures Figure 1 Cont...

Page 3: ...nerator is off line the display will show total accumulated generator hours The FROG D built in safety features include current overload voltage uctuation and high hydraulic oil temperature warnings F...

Page 4: ...with the FROG D 3P The current sensors are identical and they can be used either to measure line 1 line 2 or line 3 current draw Run the wires from the main circuit breaker to the current sensors one...

Page 5: ...tput voltage on the selected line AMPS Display Shows the current in ampers on selected line MODE Button Press to show total generator hours and hydraulic oil temperature LINE Button The LINE button al...

Page 6: ...ark mounting location for display module panel cutout and mounting screw holes Make sure there is clearance behind the panel for the module and cables before cutting holes Refer to Figure 2 for layout...

Page 7: ...FDA300 Rev0306 7 Figure 2 Display Module Mounting Dimensions Mounting holes are clearance or tapped for 10 32 screws 4 25 4 25 3 5 3 5 2 38 75 3 72 Panel Cutout A 3 75 hole is recommanded...

Page 8: ...t to mount the sensors in the circuit breaker box For each line that is to be monitored run the wire from the generator through the current sensor to the input side of the circuit breaker Refer to Wir...

Page 9: ...l Optional Hydraulic Oil Temperature Sensor The hydraulic oil temperature sensor FRC part number XE FDT2 has 1 8 27 NPT male threads Refer to Wiring section Install Optional Buzzer Install the buzzer...

Page 10: ...d An optional audible buzzer can also be connected for audio warning Voltage Out Of Range Warning If the output voltage is below 200 VAC or above 270 VAC the VOLTS readout will begin to ash This will...

Page 11: ...o the chart next to the LINE window Note When line selections 4 5 and 6 are active the AMPS window will show 3 dashes Leave the display in Auto during normal operations to monitor voltages and current...

Page 12: ...en Buzzer GND Blue Buzzer 12V Current Sensors A Current Sensor Cable Connector Pin Wire Description 1 Red Line 1 Sensor WHT 2 Black Line 1 Sensor BLK 3 White Line 2 Sensor WHT 4 Green Line 2 Sensor BL...

Page 13: ...Black Wires Blue Wires Black Wire Red Wire Current Sensors Current Sensor Cable See Sheet 1 Figure 5 Wiring Sheet 2 of 2 Red Wire Black Wire White Wire Green Wire Blue Wire Brown Wire Line 2 Line 3 Wh...

Page 14: ...rmers Current Sensors From Generator 6 Pin Deutsch Receptacle to Transformer Cable 6 Pin Deutsch Receptacle to Current Sensor Cable Refer to Figure 5 for pin number and wire color A B C N 2 4 0 v 2 4...

Page 15: ...mers Current Sensors From Generator A B C N 2 4 0 v 2 4 0 v 240v 208v 1 2 0 v Delta Circuit 1 2 0 v 6 Pin Deutsch Receptacle to Transformer Cable 6 Pin Deutsch Receptacle to Current Sensor Cable Refer...

Reviews: