Franklin Fueling Systems EVO Series Reference Manual Download Page 7

7

Relay Module

The relay modules have two styles: a 10-amp module and a 2-amp module. The 2-amp module 

is a non-intrinsically safe module that has 8 identical 2-amp SPDT (Single Pole Double Throw) 

output relays. The 10-amp module has 6 identical 10-amp SPDT output relays. Each channel 

has a fuse and three terminals. Each channel can be configured as normally open or normally 

closed, with the power off, by wiring to the appropriate terminals. The relay module provides 

another method of controlling a submersible turbine and can be used instead of TPI. The relay 

programmed to control a submersible will send a high voltage motor activation signal to the 

submersible controller to activate the turbine. This input programming is identical to TPI input 

programming in which positive shutdown occurs when a programmed input is in an alarm state.

•  AC input module- hook signals (hook isolation) for dispenser 1-2, 3-4 Unleaded

• 

4-20mA- LS500 line leak transducer (required for Electronic Line Leak Detection (ELLD))

• 

Provide ability to energize turbine for testing and disable turbine in event of ELLD 

alarm (positive shutdown)

• 

2-Wire sensor module- 2 wires sensors located in unleaded STP (sump) and dispenser 

1-2,3-4

• 

Sensor inputs programmed as inputs to a STP utilizing relay module channels will 

disable the submersible in the event of an alarm and reenable once alarm clears 

(positive shutdown).

• 

3-wires sensors can be used the same way as 2-wire sensors but will disable the 

submersible for any of the alarms associated with a 3-wires sensor. An individual 

alarm such as product, cannot be isolated for positive shutdown. (Alarm-specific 

shutdown with 3-wire sensors is explained in the section on logic conditions.)

NOTE: ELLD is not mandatory for this feature to work.

  

  

• 

A relay module can be wired two ways. Normal relay states can be wired as Normally Open or 

Normally Closed (NC). When wiring relays for Positive shutdown, use Normally Open for safety 

and simplicity. If NC relays are required, contact FFS Technical Service.

Summary of Contents for EVO Series

Page 1: ...EVOTM SERIES AUTOMATICTANK GAUGES POSITIVE SHUTDOWN REFERENCE GUIDE ...

Page 2: ... industry practices and the instructions in this manual Before you work with or install the equipment covered in this manual or any related equipment read this entire manual particularly the following precautions IMPORTANT To help prevent spillage from an underground storage tank make sure the delivery equipment is well maintained that there is a proper connection and that the fill adaptor is tigh...

Page 3: ...ump Interface TPI and various other means of programming the EVO TM Series AutomaticTank Gauge ATG console including Rules Logic Conditions and settings within specific applications The following methods are covered Use of programmed Inputs TPI and relays EVO 550 5000 Use of Shutdown On Alarm in Pumps configuration EVO 200 400 600 6000 Use of logic conditions Use of Rules engine Application specif...

Page 4: ...4 Intentionally Blank ...

Page 5: ...trollers to the corresponding terminals gnd On the EVO Series Console theTPI port has 5 total spaces The first two terminals A and B are not used for TPI applications For EcoVFCs and MagVFCs that are functioning in a group scenario Leveling Priority None the 4 Frequency terminal should be connected between the two VFCs This allows for frequency data to be transferred Each controller is then given ...

Page 6: ...leaded STP sump and dispenser sump 1 2 3 4 Sensor inputs programmed as inputs to a STP utilizingTPI will disable the submersible in the event of an alarm and reenable once alarm clears positive shutdown 3 wires sensors can be used in same manner as 2 wire sensors but will disable the submersible for any of the various alarms associated with a 3 wires sensor An Individual alarm such as product cann...

Page 7: ... 3 4 Unleaded 4 20mA LS500lineleaktransducer requiredforElectronicLineLeakDetection ELLD Provide ability to energize turbine for testing and disable turbine in event of ELLD alarm positive shutdown 2 Wire sensor module 2 wires sensors located in unleaded STP sump and dispenser 1 2 3 4 Sensor inputs programmed as inputs to a STP utilizing relay module channels will disable the submersible in the ev...

Page 8: ...NC7 NO6 C6 NC6 NO5 C5 NC5 NO4 C4 NC4 NO3 C3 NC3 NO2 C2 NC2 NO1 C1 NC1 Relay Module disables the hook signal to the pump upon alarm conditions 110 240 VAC Electrical Panel Line Neutral Switching Current 2A Max Switching Power 1500 VA Max NOTE A valid dispenser hook signal shown in the Dispenser Hook Signals section coming from the AC Input Module is required for these diagrams to function as shown ...

Page 9: ...r Relays Each Pump has a section called Shutdown On Alarm by adding alarms in this section specific sensors or even specific alarms from a given sensor can be assignedtoperformpositiveshutdownoneachpump Inthisexample settingEventCode Any will cause the pump to be shutdown whenever the assigned sensor is not in its normal or OK state ...

Page 10: ...10 Intentionally Blank ...

Page 11: ...g of a submersible turbine For example the owner operator may want the submersible turbines to be disabled for 3 wire sensor unleaded sump product alarm or at a tank level alarm unleaded tank of Low or low low All required alarms in this scenario can be included under one condition to disable a specific turbine unleaded STP An additional condition can be created to disable all submersible turbines...

Page 12: ...12 Conditions ...

Page 13: ... the other method TPI or Relay for submersible motor control Condition outputs are programmed outcomes based on the status of any programmed condition inputs These outputs will have an Invert Input to dictate the desired ActionType in programming To invert an action is to program the opposite action as programmed Enable inverted is Disable ...

Page 14: ...14 Intentionally Blank ...

Page 15: ...ensor Alarm and the UNL Pump disables as the Action Rule 2 has an Event Sensor Alarm and then clears with Rule 4 The pump will then be enabled even though Rule 1 Sensor Alarm is still active Once an event happens the action is performed any future event will supersede the initial event and act based on the rule as programmed Rules are isolated events and actions will respond according to individua...

Page 16: ...16 Intentionally Blank ...

Page 17: ...r sections of the specific applications ELLD The ELLD Electronic Line Leak Detection positive shutdown for a 3 GPH gross Line leak fail is hardcoded into the software as this is an EPA requirement As you can see in the example below thatpositiveshutdownformprecisiontesting 1 2 isalsoavailablebysettingshutdownontest fail to Yes Testing Positive Shutdown The best and quickest way to verify positive ...

Page 18: ...Intentionally Blank ...

Page 19: ...Intentionally Blank ...

Page 20: ...10000007526 r1 ...

Reviews: