background image

3 INSTALLATION AND PREPARATION

3.1 Ambient temperature

Maximum: +40 

º

C.

Should the temperature of the pumped liquid exceed 

  

40 

º

C, or in case of use at high altitude (higher than 

1000 meters), the motor power reduces due to the 
reduced density of air useful to cool the same. In some 
cases, it may be necessary to replace the motor with 
one with greater power.

Here below there is an aproximate diagram 
concerning the yield of the motors according to altitude                                     
or temperature.

3.2  Minimum suction pressure

Check the characteristic curves of the pumps to assess 
the NPSH factor and avoid cavitation problems (fig. 1 
case B).

3.3  Maximum pressure during suction

It is important to keep the sum of the inlet and of the 
outlet pressure, this latter against closed valve, always 
lower than the maximum operation pressure allowed by 
the pump (fig. 1 case A).

3.4  Minimum rate flow

The operation of the pump at a lower level than 
the minimum rate flow allowed can cause excessive 
overheating and damage the pump.

The pump must never operate against a 
closed delivery valve. 

3.5  Power supply data

See motor nameplate.

4 INSTALLATION

Legend figure 1:
1-  Filter
2-  Bottom valve
3-  Gate valve
4-  Pressure gauge
5-  Check valve
6-  Floating device
7-  Anchorings for pipings

500

1000

1500

2000

2500

3000

3500

60

70

80

90

100

110

40

45

50

55

60

T       °C

ambient
max

H        m

altitude
max

P/Pn %

There can be two relevant application cases:
-  Case shown in fig. 1.A: Pump under pressure, which 
both from a tank as shown in figure and from civil 
waterworks system, shall allow the plant to foresee a 
protection against water lack (see fig. 1.6).
-  Case shown in fig. 1.B: Pump in suction.

4.1 Assembly

Install the pump in an accessible place, protected 
against frost and as close as possible to the water 
suction point.
The pump must be tightly fastened to the basement by 
means of bolts, for the measures of the holes and their 
distance between centres, see the table on page 5.
To minimize the noise generated during the operation, it 
is suggested to assemble the anti-vibration joints on the 
tie rods fastening the base to the flooring.
Before proceeding to the final tightening of the pump, 
make sure that it is in vertical position, otherwise adjust 
the position with proper shims.
On the base of the pump it is indicated, by means of 
arrows, the inlet and output direction of the pumped 
fluid. On the lantern there are the arrows indicating the 
motor rotation direction.
The pump can be assembled vertically or horizontally, 
in any case it must not be placed vertically with motor 
located in the lower part.
To avoid unnecessary stresses on the pump body, 
place some support brackets (see fig. 1.7) in order to 
support the incoming and outcoming pipe.
To avoid air blows affecting the pump operation, foresee 
an inclination of the incoming pipes not lower than 2%.
Protect the pump against possible water hammers 
by means of a check valve (bottom valve). Install a 
shut-off valve upstream and downstream of the pump 
in order to allow its insulation in case of maintenance                     
and disassembly.

4.2 Electric connections

The electric connection must be carried out 
by qualified technicians in compliance with 
the regulation in force in the countries of 
installation of the pump.

Before replacing the cover of the terminal board and 
removing / disassembling the pump, make sure power 
supply has been disconnected.
The data concerning motor power supply are given on 
the rating plate of the same. Before starting the motor, 
check that electric power supply complies with the 
features of the same.
For the connections, use electric cables complying with 
local regulations.

When observed from above, standard 3VR, 
5VR and 9VR pumps should rotate clockwise, 
16VR should rotate counter-clockwise.

If necessary, the motor can be rotated on its axis to ease 
the access to the same by maintenance technicians. 
In this case, it is necessary to unscrew the screws 
tightening the motor on the pump, remove the joint 
covering safety carter and rotate the motor on its seat 
paying attention not to remove the coupling joint.

2

Summary of Contents for VR Series

Page 1: ...onal accessories 1 3 Applications VR centrifugal multi stage pumps are suitable for a wide range of applications They can be used in agriculture as well as in the civil and industrial field as for example water tank watering irrigation high pressure washing fire fighting protection air conditioning etc 1 4 Pumped liquids Clean liquids compatible with the construction materials of the pump not cont...

Page 2: ...e 5 To minimize the noise generated during the operation it is suggested to assemble the anti vibration joints on the tie rods fastening the base to the flooring Before proceeding to the final tightening of the pump make sure that it is in vertical position otherwise adjust the position with proper shims On the base of the pump it is indicated by means of arrows the inlet and output direction of t...

Page 3: ...of a constant liquid flow from the cap before closing it again in order to avoid the contact with the liquid 5 1 2 Pump in suction see figure 1 B and figure 3 A B and C 1 Close the gate valve on the pump delivery side in order to prevent the flow in the circuit of the fluid that is being used to fill the pump and open the gate valve on the suction side 2 Remove the upper drainage cap see fig 3 A a...

Page 4: ...w and then a Calibration of the thermal relay too low Calibrate the motor starter correctly b Low voltage during the peaks Check power supply 7 4 The flow rate is not constant a Pressure too low during suction cavitation Check the NPSH of the pump b Suction manifold pump partially obstructed by impurities Clean the pump or the suction manifold c The pump sucks air Check the suction conditions 7 5 ...

Page 5: ...ump Type F Version Round T Version Oval V Version Vitaulic C Version Flexi Clamp L mm H mm DN L1 mm L2 mm B1 mm B2 mm ø D mm L mm H mm D Rp L mm H mm D mm L mm L mm D1 mm D2 mm 3VR 250 75 25 100 150 180 210 13 160 50 1 1 4 210 50 42 2 162 50 59 36 5VR 250 75 32 100 150 180 210 13 160 50 1 1 4 210 50 42 2 162 50 59 36 9VR 280 80 40 130 200 215 250 13 200 80 1 1 2 261 80 60 3 202 80 87 40 16VR 300 9...

Page 6: ...Fig 1 2 4 230 200 150 100 50 0 12 14 16 0 6 8 10 4 3 5 3 1 3 3 A B 1 2 6 7 7 2 3 6 ...

Page 7: ...Fig 2 1 2 A B C Fig 3 7 ...

Page 8: ...placement product are the responsibility of the purchaser THIS WARRANTY SUPERSEDES ANY WARRANTY NOT DATED OR BEARING AN EARLIER DATE ANY IMPLIED WARRANTIES WHICH THE PURCHASER MAY HAVE INCLUDING MERCHANT ABILITY AND FITNESS FOR A PARTICULAR PURPOSE SHALL NOT EXTEND BEYOND THE APPLICABLE WARRANTY PERIOD IN NO EVENT SHALL FRANKLIN ELECTRIC BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES This warra...

Reviews: