12
Default (On / Off)
Trip Point Settings
Timeout Settings
Default Setting
Adjustable Range
Default Setting
Adjustable Range
General Parameters
Min
Max
Increment
Min
Max
Increment
minutes / seconds
Restart Attempts - Underload
On
3
0
10*
1
Restarts
Restart Attempts - All Other
On
3
0
10*
1
Restarts
Time Between Starts
1
0
10
1
min
Power Up Delay
30
10
120
10
sec
Speci
fi
c
Parameters
Underload
On
65%
30%
100%
5%
of SF
A
30
10
120
10
min
Overload
On
125%
80%
125%
5%
of SF
A
10
5
60
5
min
Undervoltage
Of
f
90%
80%
90%
2%
of V
rated
1
1
15
1
min
Overvoltage
Of
f
110%
110%
120%
2%
of V
rated
1
1
15
1
min
Curr
ent Unbalance
Of
f
5%
2%
10%
1%
10
5
60
5
min
Overheated Motor
On
10
5
60
5
min
False Start (Chattering)
O
n
10
0
0
0
starts in 10 sec.
1
1
15
1
min
* Unlimited r
estarts (
**
) may also be selected.
Programmable Options
Summary of Contents for submonitor
Page 6: ...Installation Operation Manual ...