MAINTENANCE
Troubleshooting
43
F22
Control Board Fault
• EEPROM error
• Bluetooth error
• Cycle power to see if fault resets.
• Check cable connection between Control Board and Power
Board. Check all programming parameters.
• Verify all programming parameters
• Reset the drive to factory default settings, refer to
.
• If problem persists, note the sub-fault number on the display
before contacting the FE Service personnel.
F25
Moisture Sensor Fault • Moisture Sensor has detected
moisture or water
• External device wired to the WET
SENSOR terminal has satisfied
the configured fault condition
• Input is incorrectly configured
• Check Moisture Sensor location for moisture or presence of
water. Clean and dry area. Drive will restart when moisture or
water is no longer detected.
• Ensure Moisture Sensor input is configured/wired correctly
F27
Pressure Transducer
Error
• Pressure transducer has failed
• Pressure transducer is incorrectly
wired
• Pressure transducer signal is
outside of the expected range
• Pressure transducer is
disconnected
• Incorrect sensor type setting
• Check pressure transducer wiring connections; tighten or
correct, if necessary
• Ensure sensor type setting is correct
• Replace pressure transducer
F28
Real Time Clock Fault
not displayed, but
logged.
• Internal real time clock is not
programmed
• Real time clock battery on
Control Board is loose
• Real time clock battery is dead
• Ensure battery is properly inserted. If corrected, reconnect to
drive using mobile app to reset the internal clock time
• Replace battery. If replaced, reconnect to the drive using the
mobile app to reset the internal clock time
F29
RTD Temperature
Alarm
• Motor windings are getting hot
• Shut off the system to allow the PMA to cool down
F30
RTD Temperature
Fault
• Motor windings are too hot
• Shut off the system to allow the PMA to cool down.
• Persistent faults may require pulling the PMA and installing a
cooling sleeve (AIM manual)
F31
Input Phase Loss
• DC bus ripple amplitude exceeds
a set value
• Input phase imbalance and loss of phase may indicate similar
issues
• Measure and confirm adequate voltage at the drive input (L1-
L2, L2-L3, and L3-L1).
• Confirm input power leads are properly inserted into the input
power terminal block and confirm proper torque.
F32
No Motor
• All three phases have current
below 15% of motor FLA for
250 ms
• Motor circuit has open or loose
connection
• Troubleshoot motor
• Tighten motor connections
F35
Incompatible Firm
-
ware
• Firmware of Power board and
Control board are incompatible
• Update firmware of boards to latest version
Code
Fault
Possible Cause
Corrective Action