background image

2 Installation instructions

2.1 Warning to the user

All the local and national regulations, and in
particular those relating to national and European
standards, must be observed when installing the
appliance.
An incorrectly installed heating appliance can
cause serious accidents

(chimney fires, burning of

plastic insulation materials, in partition walls, etc.).

The insulation of both the appliance and the
exhaust gas pipe has to be reinforced

and done

a c c o r d i n g t o t h e S t a n d a r d s a n d t h e B u i l d i n g
Regulations for safety reasons. The installation must be
carried out according to the Standards and the Building
Regulations.
Failure to respect the mounting instructions leads to
engage the responsibility of the one doing the
installation.
The manufacturer’s responsibility shall be limited to the
supply of the appliance.

2.2 Location of the unit

Ventilation :

For satisfactory appliance operation with

a

natural draught

, check that sufficient air for

combustion is available in the room. In houses
equipped with one VMC (controlled mechanical
ventilation), this one aspire and renew the ambient air;
in this case, the residence is under slight low pressure
and a

non-sealable

external air intake must be

installed in addition to the chimney itself, at least 50cm²
in section.

Position of the unit :

For new installations, select a

central position within the house, to provide a good heat
distribution around the building. The heat distribution
towards the other rooms will be made through the
communicating doors. These rooms must be at low
pressure or fitted with

non-adjustable air registers,

placed so that they cannot be obstructed

, to

encourage circulation of the hot air.

Floor and walls :

Make sure there are not combustible

or covered with combustible material. Otherwise it must
necessary to install a non-combustible protection.
T h e r e

m u s t

b e

a

clearance of at least 150
mm at each side of the
appliance and at the back
of the appliance from a
n o n - c o m b u s t i b l e w a l l .
This distance must be
extended to a minimum
clearance of 400 mm from
a n y

c o m b u s t i b l e

m a t e r i a l s .

T h i s

m e a s u r e m e n t m a y b e
reduced to a minimum
gap of 50 mm when the
non-combustible wall is at
least 200 mm thick.
There should ideally be a
minimum gap of 300 mm
at the right hand side of
the stove, this will ensure
the best possible access

to the loading door. When using a single wall flue pipe,
there must be a clearance (A) of at least three times its
diameter (B) from any combustible materials. If the
appliance has to be located in an opening, this distance
must be extended to a minimum clearance (A) of 450
mm from the pipe or the stove body to any combustible
materials.

Hearth :

The appliance must stand on a fireproof

hearth.
It is possible to provide a hearth made of non
combusible board/sheet material or tiles at least 12 mm
thick (C).
Constructional hearths should be constructed of solid
non combustible material at least 125 mm thick
(including the thickness of any non combustible floor
under the hearth).
The hearth must protrude at least 300 mm in front of the
stove and 150 mm each side.
Hearths are provided to prevent combustion appliances
setting fire to the building fabric and furnishings and to
limit the risk of people being accidentally burnt.
Therefore, they should be separated from adjacent
combustible materials and should be satisfactorily
delineated from surrounding floor finishes (carpets etc.)
as follows.
Combustible material should not be placed under a
constructional hearth for a solid fuel appliance within a
vertical distance of 250 mm from the upper surface of
the hearth, unless there is an airspace of at least 50 mm
between the combustible material and the underside of
the hearth.
Where a superimposed hearth has been placed onto a
constructional hearth, combustible material placed on
or besid the constructional hearth should not extend
under the superimposed hearth by more than 25 mm or
closer to the appliance than 150 mm.
E n s u r e

t h a t

t h e

h e a r t h

( s u p e r i m p o s e d

o r

constructional) is suitably delineated to discourage
combustible floor finishes from being laid too close to
the appliance, by marking the edges or providing a
change of level.

4

Technical manual “1220”

“ARDENNES” - model 134 15 02

Installation instructions

1 5 0

1 5 0

1 5 0

3 0 0

1 5 0

B

A

A

C

1 5 0

Figure 2 - Minimum clearances

Summary of Contents for ARDENNES 134 15 02

Page 1: ...34 15 02 Output 15 kW EN FR NL IT Technical manual to be saved by the user for future reference STAUB FONDERIE SARL with the capital of 6 359 540 Head Office Address 2 rue Saint Gilles 68230 TURCKHEIM...

Page 2: ...Lighting p 7 Operating procedure p 8 De ashing p 8 Maintenance of the Chimney p 8 Maintenance of the stove p 8 Safety advice p 8 Trouble shooting p 9 Spare parts p 10 FRANCO BELGE congratulates you on...

Page 3: ...m tests carried out in accordance with standard EN 13240 with logs of 12 cm of depth 40 cm and a draught of 12 Pa fuel mass of 5 kg 1 3 Appliance description Wood stove in conformity with EN 13240 int...

Page 4: ...ible materials This measurement may be reduced to a minimum gap of 50 mm when the non combustible wall is at least 200 mm thick There should ideally be a minimum gap of 300 mm at the right hand side o...

Page 5: ...e at least 4 5 m 15 ft high and be at 40 cm above the ridge of the roof and 8 meters away from any construction In case of a flat roof or when the roof gradient is lower than 15 the stack must be 1 2...

Page 6: ...on pipe and any draught stabiliser must have access for cleaning 2 7 Pre utilisation check Check that the seals of the smoke line are in good condition Check that the door closes correctly Check that...

Page 7: ...and the flue soot tar etc Recovered wood Railway sleepers telegraph poles offcuts of plywood or chip board pallets etc Burning treated wood quickly clogs the flue ways soot tar etc pollutes the envir...

Page 8: ...fuel at least once a year Ensure the flue pipe connection is also cleaned In case of a chimney fire you must act to cut off the air supply to the chimney This can be done by shutting the door of the...

Page 9: ...not continuously burn small wood sticks bundles carpentry offcuts plywood pallets etc Smokes when lighting up Flue duct is cold Burn paper and kindling wood to increase heat Room is in decompression n...

Page 10: ...Gasket 10 Y L B P E C N Q 1 50 m 19 181634 Gasket 15 Y L B P E C N Q 1 85 m 20 188851 Ceramic glass Y L B P E C N Q 02 21 189825 Screw M5x6 Y L B P E C N Q 03 22 207315 Back panel Y L B P E C N Q 01 2...

Page 11: ...2 4 9 1 0 1 4 3 4 5 4 3 7 4 8 4 2 3 6 2 2 9 3 9 2 4 5 0 5 7 3 1 3 0 5 8 3 3 2 1 5 9 1 8 3 2 3 2 1 1 2 2 1 4 8 1 8 1 9 7 5 1 1 7 2 0 2 7 1 1 2 5 5 9 7 5 2 1 9 1 7 2 0 1 1 2 5 2 7 4 7 5 6 1 6 1 5 4 1 5...

Page 12: ...08 EF Ash pan guide Y 01 47 327908 EP Ash pan guide N 01 47 327908 MK Ash pan guide C 01 47 327908 RH Ash pan guide P 01 47 327908 RJ Ash pan guide B 01 47 327908 RP Ash pan guide E 01 47 327908 ER As...

Page 13: ...Right Complete door P 01 58 988976 Right Complete door E 01 58 988978 Right Complete door C 01 58 988980 Right Complete door N 01 58 989001 Right Complete door Q 01 59 988969 Left Complete door Y 01 5...

Page 14: ...ion of closed combustion fireplace and inserts for which our guarantee is 5 five years excluding the following 1 Indicator lights fuses electrical elements and fans 2 Parts subject to wear or in conta...

Reviews: