Enter the Programming Mode
Press the F1 or the F2 key repeatedly, in the normal running mode, until the following screen is
shown. This enters the programming mode:
F1 F2 F3 F4
Press YES (F4) and then the following screen will prompt the user to enter the password if
enabled:
F1 F2 F3 F4
Enter the correct password. Default password for Level 1 is 1234.
Press the UP (F1) or DN (F2) key to select a new digit or character, the cursor points to the
selected digit. Press NXT (F3) to select the next digit and OK (F4) to accept the entry.
If the wrong password is entered, the message “Wrong Password” will be displayed for a few
seconds and then return to the programming entry screen. If the password is accepted, the
following screen will be shown:
F1 F2 F3 F4
This is the base screen for the programming mode. To exit the programming mode, press EXIT
(F4) repeatedly until “Normal Mode” is seen briefly.
SET PARAMETERS?
NO
YES
PASWD:_
UP DN NXT OK
SET PARAMETERS?
I/O FLO DSP EXIT
BACnet Programming
Modbus/BACnet
19
BA
CNE
T PR
OGRAMMING
Modbus/BACnet