Defrost
Defrost will be initiated automatically in the hold mode at pre-set intervals.
4
To initiate a manual defrost during the hold mode press
for 5 seconds, defrost will start with
being displayed.
d
Alarm and Warnings
d
Defrost in operation
AL
Low Temperature Alarm
AH
High Temperature Alarm
PR1
Air Probe fault
PR2
Food Probe Fault
Parameter Setting and Adjustment
Setting the configuration parameters
The parameters are arranged on two levels
Access to the First Level
To access the parameters the controller must be in the stand-by mode.
To place the controller in ‘stand–by’ press
for 2 seconds, whilst in stand-by the cabinet internal air
temperature will be displayed intermittently.
Press
and
for 4 seconds the display will show ‘
PA
’.
Press ‘
r0
’ will be displayed.
Press
to display the value followed by
to decrease the value or
to increase the value.
Press
to return to the followed by
to
move to the next parameter.
On completion of the changes press
plus
to exit or wait 60 seconds
First Level Configuration Parameters
Mnem.
Definition
Min.
Max
Default
Dim.
FXBC
r0
Parameter r7, r8, r9 and Ra hysteresis
0.1
15.0
2.0
°K
2.0
r1
Timed positive blast chilling duration
1
600
90
min.
90
r2
Timed negative blast chilling duration
1
600
240
min.
240
r3
Positive blast chill end point temperature (food probe)
-99.0 99.0 3.0
°C
3.0
r4
Negative blast chill end point temperature (food probe)
-99.0
99.0 -18.0 °C -18.0
r5
Set temperature positive blast chilling duration
1
600
90
min.
90
r6
Set temperature negative blast chilling duration
1
600
240
min.
240
r7
Positive blast chilling setpoint (air temp.)
-99.0
99.0
0.0
°C
0.0
r8
Negative blast chilling setpoint (air
temp.)
-99.0
99.0 -40.0 °C -25.0
r9
Post positive blast chilling storage setpoint
-99.0 99.0 2.0
°C
2.0
rA
Post negative blast chilling storage setpoint -99.0
99.0
-20.0 °C -20.0
Summary of Contents for FX Blast Chiller
Page 1: ...FX BLAST CHILLER ISO 14001 ISO 9001 ...
Page 9: ...FXBC 10 Wiring Diagram 8 ...
Page 10: ...FXBC 10R Wiring Diagram 9 ...
Page 11: ...FXBC 20R Wiring Diagram 10 ...
Page 12: ...FXBC 20R Wiring Diagram 11 ...
Page 13: ...FXBC 30 Wiring Diagram 12 ...
Page 14: ...13 FXBC 30R Wiring Diagram ...
Page 15: ...FXBC 40 Wiring Diagram 14 ...
Page 16: ...FXBC 40R Wiring Diagram 15 ...
Page 17: ...16 ...
Page 18: ...17 ...
Page 19: ...18 ...