P13 Change
Temp
The percentage of a temperature based chill cycle, which is passed before automatically adjusting the air
temperature set point to 1°C.The range is adjustable in 5% increments.
Range 5% to 95%.
Hard Max
P14 Air
Temp
The temperature, which the air probe must read before the condensing system is de-energised in the chill mode
of the Hard Chill Max Program.
Range -20°C to 15°C.
P15 Chill
Time
The period Hard Chill Max program is in chill mode prior to entering Hold mode in a time based chill cycle.
Range 5 minutes to 480 minutes.
P16 Chill
Temp
The temperature, which the Food Probe 1 must read before the condensing system is de-energised in the chill
mode of the Hard Chill Max program prior to entering the Hold mode of a temperature based cycle.
Range -15°C to 15°C.
P17 Hold
Temp
The temperature, which the air probe must read before the condensing system is de-energised in the Hold mode
of the Hard Chill Max program.
Range -15°C to 15°C.
Shock Freeze
P18 Air
Temp
The temperature, which the air probe must read before the condensing system is de-energised in the chill mode
of the Shock Freeze Program.
Range -35°C to 15°C.
P19 Chill
Time
The period Shock Freeze program is in chill mode prior to entering Hold mode in a time based chill cycle.
Range 5 minutes to 480 minutes.
P20 Chill
Temp
The temperature, which the Food Probe 1 must read before the condensing system is de-energised in the chill
mode of the Shock Freeze program prior to entering the Hold mode of a temperature based cycle.
Range -15°C to 15°C.
P21 Hold
Temp
The temperature, which the air probe must read before the condensing system is de-energised in the Hold mode
of the Shock Freeze program.
Range -35°C to 15°C.
Professional 1
P22
Air Temp Std
The standard temperature, which the air probe must read before the condensing system is de-energised in the
chill mode of the Professional 1 Program.
Range -20°C to 15°C.
P23
Chill Time Std
The standard period Professional 1 program is in chill mode prior to entering Hold mode in a time based chill
cycle.
Range 5 minutes to 480 minutes.
P24
Chill Time Minimum
The minimum period Professional 1 program is in chill mode prior to entering Hold mode in a time based chill
cycle that it can be adjusted to by the operator.
Range 5 minute to 60 minutes.
P25
Chill Time Maximum
The maximum period Professional 1 program is in chill mode prior to entering Hold mode in a time based chill
cycle that it can be adjusted to by the operator.
Range 60 minute to 480 minutes.
P26
Chill Temp Std
The standard temperature, which the Food Probe 1 must read before the condensing system is de-energised in
the chill mode of the Professional 1 program prior to entering the Hold mode of a temperature based cycle.
Range -15°C to 15°C.
Summary of Contents for BC 21
Page 1: ...RBC20 60 Blast Chiller ...
Page 24: ...23 COMPRESSOR WIRING RBC20 60 ...
Page 25: ...RBC20 60 1 of 2 Wiring Diagram 24 ...
Page 26: ...RBC20 60 2 of 2 Wiring Diagram 25 ...
Page 27: ...RBC20 60R 1 of 2 Wiring Diagram 26 ...
Page 28: ...27 RBC20 60R 2 of 2 Wiring Diagram ...
Page 29: ......
Page 30: ...2 ...
Page 31: ...3 ...