LED Output 

ATOM Interlocking Device state is indicated by LED at the base of the device. If a device is in a fault state, a full cycle of the 

inputs or power cycle may be required to clear the fault state. If fault state cannot be cleared contact Fortress Technical 

Support.

Led 

Pattern

Status 

State

Cause 

Troubleshooting

Safety Output State
Safety 

on Guard 

Locking 

(SOGL)

Safety on 

Guard

(SOG)

Off

Off

No power supply

Check continuity from 

power supply to device

Low

Low

Green

Locked

High

High

Green / Red

Unlocked, 

Actuator In

Low

High

Red

Actuator 

Out

Low

Low

Red Flash

Overridden Auxiliary release left in 

unlocked position

Check that the auxiliary 

release has been rotated 

fully anti-clockwise

Low

High

Green Flash

Safety 

Inputs Low

Safety Input signal from 

previous device low

Check the safety state of 

the previous device, or 

continuity from the 24V 

supply if the first device in 

the chain

Low

Low

Amber

Unlocking 

Fault

Unable to unlock, possibly 

due to tension on actuator

Check for any obstruction 

of the mechanism.

Press actuator tightly 

towards the device to 

release any tension

Low

High

Amber Flash

Safety 

Input Fault

Mismatch between two 

safety input signals

Confirm continuity from the 

previous device on both 

safety inputs, then reset 

fault by cycling the safe 

state of the previous device

Low

Low

2 Amber 

Flash

Safety 

Output 

Fault

Short circuit on safety 

output signals

Confirm the safety outputs 

are not shorted together, or 

to any other signal

Low

Low

3 Amber 

Flash

Wrong 

RFID 

Actuator 

Used

Actuator from another 

device used by mistake

Confirm serial number of 

actuator matches that of 

the device

Low

Low

Long Amber 

+ Flash

Locking 

Fault

Device unable to lock

Check for any obstruction 

of the mechanism. 

Press actuator tightly 

towards the device to 

release any tension.

Low

High

Long Amber 

+ 2 Flash

RF Lost 

Whilst 

Locked

RF signal from actuator 

lost whilst in the locked 

state

Check that mechanism has 

not been rotated without 

the actuator – see 

instructions on Actuator 

Does Not Enter.

Low

Low

Long Amber 

+ 3 Flash

Under /

Over 

Voltage

Insufficient supply voltage 

to device.

Measure the supply 

voltage at the device is 

within specification

Low

Low

8

Summary of Contents for ATOM

Page 1: ... invalidates all warranties The Device must be installed in electrical installations meeting the requirements of the applicable IEC standards The Device is not to be used as a Mains Isolator or Emergency Stop The Device is a component to be added to a permanent electrical installation meeting the requirements of the applicable IEC EN standards All the voltages used within the connected circuits mu...

Page 2: ...uator is engaged or removed Part No Solenoid Locking Type Switch Configuration M12 Connector Types Optional Escape Release ATM 100A1 A Power to release unlock Safety on Guard Locking SOGL Single 5 Pin M12 No ATM 100A2 A Power to release unlock Safety on Guard Locking SOGL 2 x 5 Pin M12 in Daisy Chain configuration No ATM 100A3 A Power to release unlock Safety on Guard Locking SOGL Single 8 Pin M12...

Page 3: ...thstand Voltage Uimp 500V Voltage Drop Ud 3 5V Rated Operating Currents 400mA Minimum Operational Current 100mA Off State Current 0 5mA Rated Conditional Short circuit Current 100 A Overvoltage Category Type 2 Electromagnetic Compatibility EMC Conforms to BS 60947 5 3 To Meet UL Requirements The device must be connected to a Limited Voltage Current Circuit A 4A fuse must be fitted to the device po...

Page 4: ...TOM_PIN_OUT_INFO DATE 17 03 22 THE COPYRIGHT OF THIS DRAWING BELONGS TO FORTRESS INTERLOCKS Ltd THE CONTENT OF THIS DRAWING IS CONFIDENTIAL AND MUST NOT BE DISCLOSED TO ANY 3rd PARTY WITHOUT OUR SPECIFIC WRITTEN APPROVAL ATOM CONNECTOR PIN OUT INFORMATION RELEASE LEVEL Approved for Production TITLE SCALE 2 00 ISSUE 0 A ATOM CONNECTOR POSITIONS 4 5 3 1 2 SINGLE 5 PIN M12 CONNECTOR ATM 100A1 A ATM 1...

Page 5: ...ened For Safety on Guard SOG devices the monitors is activated when the device is unlocked Daisy Chain information The number of devices that can be wired in series depends on two main criteria 1 Power line voltage drop 2 Total Safety Response Time Voltage Drop Safety Response Time Each ATOM Device in series draws current and causes a voltage drop on the power line The greater the number of device...

Page 6: ...acing the Device into its Locked State Unlocking The Device is unlocked when voltage is applied to the Solenoid Drive pin Opening Once unlocked the ATOM Actuator assembly can be removed from the ATOM Switch assembly Auxiliary Release Function In the event of power failure the ATOM Interlocking Device can be released and unlocked using the supplied Auxiliary Release Driver Bit irrespective of the s...

Page 7: ...housing M12 cable s entry Manual solenoid override To reset and relock an ATOM Interlocking Device after an Escape Release operation First isolate power to the guarded machine to ensure it cannot restart when Safety Outputs go high Pull on Escape Release knob see Fig 1 Close the Gate Door of the guarded area Test that the Escape Release has been fully reset by checking status of Safety Outputs are...

Page 8: ... on actuator Check for any obstruction of the mechanism Press actuator tightly towards the device to release any tension Low High Amber Flash Safety Input Fault Mismatch between two safety input signals Confirm continuity from the previous device on both safety inputs then reset fault by cycling the safe state of the previous device Low Low 2 Amber Flash Safety Output Fault Short circuit on safety...

Page 9: ... Door Gate post to allow for Escape Release housing See Fig 10 for required hole location Note ATOM with Escape Release ER suitable for door gate post thickness up to 56mm For anything greater than 56mm an extension kit will be required please contact Fortress for more information 6 Mount the ATOM Switch and ATOM Actuator assemblies to appropriate parts of the machine or guarding The ATOM Actuator...

Page 10: ...ly M12 quick disconnect cable s M5 nylon washer M5 security fixing screw min length 45mm M5 security fixing screw min length 45mm Figure 3 Extrusion Profile Mounting Application Example M12 quick disconnect cable s essinterlocks com rtress erlocks M5 security fixing screw min length 20mm M5 T Nut M5 T Nut ATOM actuator assembly M5 security fixing screw min length 20mm M5 T Nut M5 T Nut 40mm alumin...

Page 11: ...embly ATOM actuator assembly 11 Figure 5 ATOM Device with Escape Release Mounting Example www fortress safety com FORTRESS ATOM Escape Release knob removed while mounting Escape Release housing mounted through gate post Ø 21mm min bore to accept Escape Release housing M5 T Nut M5 Nylon Washer M5 Security Fixing Screws min length 40mm M5 Nylon Washer M5 Security Fixing Screws min length 40mm M5 T N...

Page 12: ...e Escape Release knob see fig 1 and remove the ATOM Actuator from the ATOM Switch 5 Pull on Escape Release knob to reset Escape Release 6 Reinsert the ATOM Actuator into the ATOM Switch It must lock into position Power to Lock ATOM Interlocking Devices 1 Insert the ATOM Actuator into the ATOM Switch It must not lock into position Electrical Function Test Powered 1 Close the guard ensure the ATOM D...

Page 13: ...is Voided Under the Following Conditions 1 If these instructions are not followed 2 Non compliance with safety regulations 3 Installation and electrical connection not performed by authorised personnel 4 Non implementation of functional checks 13 Actuator Does Not Enter Head Correcting A Rolled Mechanism In some scenarios such as cleaning or high vibration the ATOM Interlocking Device can have the...

Page 14: ...R S Protection Against Environmental Influences In order to maintain full mechanical and electrical performance the Device must be protected against the ingress of all foreign bodies such as swarf sand blasting shot etc The Device is not suited for use in corrosive environments The Device is only suitable for dusty environments where careful consideration has been given to environment requirements...

Page 15: ... Dimensional Drawing ATOM Interlocking Device 6 7 7 138 25 13 8 72 5 32 16 6 75 41 5 5 THRU ALL 2 PLACES 33 2 36 125 5 5 125 20 16 6 5 2 THRU ALL 2 PLACES 5 2 THRU ALL 2 PLACES 40 WHEN CENTRALLY ALIGNED 6 0 15 0 7 7 THE COPYRIGHT OF THIS DRAWING BELONGS TO FORTRESS INTERLOCKS Ltd THE CONTENT OF THIS DRAWING IS CONFIDENTIAL AND MUST NOT BE DISCLOSED TO ANY 3rd PARTY WITHOUT SPECIFIC WRITTEN APPROVA...

Page 16: ...ngth Description CABLE 2M AT1 2m To suit 5 Pin M12 connectors CABLE 5M AT1 5m CABLE 10M AT1 10m CABLE 2M AT3 2m To suit 8 Pin M12 connectors CABLE 5M AT3 5m CABLE 10M AT3 10m CABLE 2M ATD 2m To suit X 5 Pin M12 daisy chain connectors CABLE 5M ATD 5m CABLE 10M ATD 10m ATOM Shorting Plug Part No Description SHORTING PLUG ATD To terminate last ATOM Device at end of daisy chain FORTRESS A company Halm...

Reviews: