Fortress Power - Sol-Ark LFP Legacy Series Inverter Guide 

 

Start V

 autostarts the grid or generator 

charge when the battery hits that voltage. It 
charges the battery to 100%. Avoid hitting 
this voltage by programming the Time-of-Use 
settings in the grid parameters.  

 

Start %

 - disabled. Do not use % mode with 

LFP-series batteires. 

 

Float V / Absorb V

 set to 54.4V 

 

Equalization 

set to 0 hours (disabled) 

 

 The amount the grid or generator charges 

the batteries. Should not be more than 80A. 

 

Grid  Charge 

 

Check

 

for grid-tied arrays or 

off-grid arrays with large generators. 

 

Gen Charge 

 

Check this box if tying a <8kW generator into the generator breaker on the Sol-Ark. 

  

 

Shut down %  - 

is the low battery cut off 

point which either shuts down the inverter or 
transfers to grid power. This value should be 
raised to 51V if there is not grid or generator 
charge on site to avoid regularly deep-
discharging the battery. Regularly cycling the 
battery below 20% will reduce the Fortress 
warranty. 

 

Low Batt 

 

provides an alert when the battery 

hits this level. User adjustable. 

Restart 

 

determines when the battery 

can be used again after reaching the 
shutdown %. 

Batt Empty V 

 Keeps a few volts in the battery to avoid locking the battery out during accidental deep 

discharges. 

 

Step 9 

 Program Grid Parameters.

 

Go back to the home screen, touch the gear icon, and select “

Grid Setup”

. The Grid Parameters menu 

will appear and the Grid Limiter Function will be the first tab. You may still need to program other tabs, 
but this Grid Limiter tab plays an important role in battery behavior. The programmed levels are user 
specific, so think carefully when programming this menu relative to the specific job site and grid policy.

 

80A 

51V 

0 Hours 

5% 

48V 

50.5V 

10% 

15% 

54.4V 

54.4V 

54.4V 

5% 

20% 

25% 

49V 

51.4V 

51.8V 