14
15
Plug in
your device to a
power outlet
using the provided
power cables.
Note:
We recommend connecting your FortiGate to an
uninterruptible power
supply (UPS)
in case of a power outage
Basic Connections - AC Model
Power Outlet
or UPS
Power Outlet
or UPS
PSU2
PSU1
Supplied Power Cable
Supplied Power Cable
WARNING:
■
This product is only intended for installation and use in a Restricted Access
Location.
■
The DC power cables are intended to be used only for in-rack wiring; must
be routed away from sharp edges, and must be adequately fixed to prevent
excessive strain on the wires and terminals.
■
DC cables must be a minimum of
12 AWG
.
■
Ensure the terminal rings are securly and safely fastened to the PSU terminals.
Supplied Grounding Lug
Ground connection
A grounding lug is provided with DC models to be used with a 12 AWG ground wire.
FortiGate
ground
connector
(green)
Chassis
ground
connector
(green)
Central office
ground system
Data
Center
ground
connector
GND
12 AWG
Basic Connections - DC Model
PSU 1
PSU 2
Power Cable (not included, min 12AWG)
Power Cable (not included, min 12AWG)
DC Power Terminals
DC Power Terminals