Instruction Manual - Power Supply Units 

Series: AVP, ACR, HFxC, HExC, HPxC, customer-specific power supply units 

 
Please read before installation and start-up! 
 

Please  read these instructions and  warnings thoroughly  before  you put the unit into operation. Retain this manual for further  reference. The  unit may only be 
installed  and  put  into  operation  by  qualified  personnel.  In  the  event  of  malfunction  or  damage,  turn  the  power  off  immediately  and  send  the  unit  back  to  the 
factory for inspection. The unit does not contain any serviceable parts. Internal fuses (if included) will only trip in case of a unit defect. The data made available 
merely describe the product and may not be regarded as warranted characteristics in a legal sense. In case of doubt the German text shall prevail.  

Intended use: 

This unit has been designed for installation in an enclosure or switchgear cabinet and is intended to be used in general electronic devices like for example for 
industrial control, office, communication, and instrumentation equipment. Some of these units are suitable only for railway applications according to EN50155. 
Please  refer  to  the  conformity  declaration  or  the  data  sheet.  Do  not  use  this  unit  in  control  systems  where  malfunction  may  cause  severe  personal  injury  or 
threaten human life.  
 

Warning  

Failure to observe the following points include the risk of electrical shock, fire, personal injury or death. 
 

8. 

Risk  of  electrical  shock!  All  types  may  only  be  installed  by  qualified  personnel  (e.g.  IEC60364,  VDE0100,  VDE0105)!  In  case  of  malfunction  or 
damage turn the power off immediately. Do not try to clear the problem yourself.  

9. 

Turn the input power off before starting any installation, maintenance or modification work and prevent it from inadvertent re-powering.  

10.  If  the  units  are  equipped  with  a  protective  conductor,  never  operate  the  units  without  said  conductor.  Make  sure  that  the  cross-section  of  said 

conductor is compliant with the established guidelines.  

11.  Prevent any foreign objects from entering the housing.  
12.  Do not open the units enclosed in a housing. There are high voltages inside.  
13.  Units in open frame construction include the risk of death! Touching of a component may cause an electrical shock! 
14.  Do not touch the housing during power-on or immediately after power-off. Hot surfaces may cause burns.  

Caution!

 

Reduction of output current may be necessary when:  

6. 

minimum installation clearances cannot be met   

7. 

altitude is higher than 2000m  

8. 

device is used above +55°C ambient temperature 

9. 

mounting orientation differs from the standard mounting orientation  

10.  airflow for convection cooling is obstructed.  

 

Installation 

9. 

Make sure that the unit is well ventilated by simple air convection or by a ventilator, to avoid overheating. A clearance of at least 10 cm must be kept 
when other heat sources are adjacent.  Please observe the maximum ambient temperature  limitations. Some power  supply units may  need forced 
ventilation by a ventilator. Please refer to the specifications in the data sheet.  

10.  Output current and output power must not exceed the rated values of the specification.  
11.  In  case  of  power  supply  units  that  are  without  protection  against  contact  (e.g.  ACR,  HFxC,  HPxC  series),  an  insulation  clearance  subject  to  the 

grounding concept of up to 10mm has to be kept.   

12.  In  case  of  power  supply  units  that  are  partially  protected  against  contact  (e.g.  AVP 

–  K/KS/KSL/KSP  series),  an  insulation  clearance  on  the 

underside of the unit of at least 5mm has to be kept and insulation material (e.g.  Mylar foil) should be applied between the power supply unit and the 
end device/system. 

13.  In  case  of  power  supply  units  that  can  be  print  mounted  and/or  require  additional  thermal  connection  via  heat  conductor  pads  (e.g.  ACR,  HFxC, 

HPxC, AVP series) the dielectric strength has to be checked after installation in an end device/system. Please refer to the specifications in the data 
sheet as to the use of heat conductor pads. 

14.  Use appropriate copper cables for wiring that are designed for a minimum operating temperature of : 

60°C for ambient temperatures up to 45°C, 
75°C for ambient temperatures up to 60°C and 
90°C for ambient temperatures up to 70°C. 

Wire end ferrules are allowed. National regulations and installation instructions have to be kept!  
 
Recommended wire cross sections:                                    

AWG 

18 

16 

14 

12 

10 

Rated current 

6A 

6-10A 

10-16A 

16-25A 

25-32A 

32-40A 

Cross-sections  
(mm²) 

0,75 

1,5 

2,5 

The maximum current above refers to  a maximum of 1  to  4 connected  wires. When using 5  or more  wires  the  rated current has to be limited to 
maximally 80%. 

 

Make sure that all strands of a stranded wire enter the terminal connection and all screws of the connection terminals are well tightened. Fasten the 
screws of unused terminals. 

15.  For  units  without  internal  fuse,  the  lead  wire  must  be  equipped  with  a  fuse  or  an  automatic  cutout  to  protect  the  wire.  For  units  with  protected 

conductor or units the metal components of which have to be grounded, a fuse or an automatic cutout may be required in each lead.  Take care that 
the fuse/the automatic cutout are suitable for the voltage to be separated and that they can reliably separate the occurring short circuit currents. If 
automatic cutouts are used, chose types with a Z-trip characteristic. For further information, please refer to the respective data sheet 

16.  All  Autronic  power  supply  units  have  been  developed  on  the  basis  of  valid  and  customer-specific  solutions  and  in  compliance  with  the  EMC 

regulations agreed upon.  Test reports are available on request. The power supply units are designed for installation in other products by qualified 
personnel. They must not be used as independent current supply. Compliance with EMC has to be verified in the end device. These products are 
intended for OEMs and system suppliers including distribution channels. They are not intended for end consumers. 