9

MZ series 

4.2 Installation of the Connection Pipe 

Connecting piping for indoor unit and outdoor unit are in manifold mode. (As shown below).

 

Fig 6 

4.2.1 Piping between the Indoor and Outdoor Units 

(1) If  the liquid and gas stop valves which have the sign of A , B, C, D or E have not been connected to the 

indoor units, please turn off the screw cap with the spanner airproof. 

(2) Refer to Fig.7 for the moments of torque for tightening screws.

(3) Let the flare end of the copper pipe point at the screw and then tighten the screw by hand.

(4) After that, tighten the screw by the torque wrench unit it clatters (as shown in Fig.7).

(5) The bending degree of the pipe can not be too small; otherwise it will crack. And please use a pipe tube 

bender to bend the pipe. 

(6) Wrap the exposed refrigerant pipe and the joints by sponge and then tighten them with the plastic tape.

P ipe

F lare N ut

S panner

Fi

g

7

1) During the connection of the indoor unit and the refrigerant pipe, never pull any joints of the indoor unit by force; 

otherwise the capillary pipe or other pipe may crack, which then would result in leakage.

2) The refrigerant pipe should be supported by brackets, that is, don

t let the unit withstand the weight of it.

3) If the piping connection size of outdoor unit does not match the piping connection size of indoor unit, use the 

piping connection dimension of indoor unit. And use different-diameter joints which is installing on the place of

the piping connection to connect the indoor unit.

4)  For the MZ system, each pipe should be labeled to tell which system it belongs to avoid mistaken

inaccurate piping.

4.2.2 Allowable pipe length and drop height among indoor and outdoor units 

If the total refrigerant pipe length (liquid pipe) is smaller than that listed in the table below, no additional 

refrigerant will be charged. 

Table 6 

Model 

FGH-42ES-MZ

Total Liquid Pipe 

Lenght (a+b+c+d+e) 

131.2ft 

Pipe

diameter

Thickness of

copper tube

Tightening

torque

1/4 inch

≥0.

0315 inch 11

22 ft·lbf

3/8 inch

≥0.

0315 inch 26

29 ft·lbf

1/2 inch

≥0.

0315 inch 33

37 ft·lbf

5/8 inch

0.0394 inch 44

48 ft·lbf

Summary of Contents for FGH-42ES-MZ

Page 1: ...OWNER S MANUAL MZ SERIES FGH 42ES MZ Thank you for choosing our product Please read this owner s manual carefully before operating the unit and keep it for future reference...

Page 2: ......

Page 3: ...ing their running modes the cooling mode is compatible with the dehumidifying mode and the fan mode can go with any other mode If the supply power fails when the unit is running then the indoor unit w...

Page 4: ...is necessary Exception Clauses Manufacturer will bear no responsibilities when personal injury or property loss is caused by the following reasons 1 Damage the product due to improper use or misuse of...

Page 5: ...3 3 Piping Connection 7 4 Installation Instruction 8 4 1 Outline and dimension of the outdoor unit 8 4 2 Installation of the Connection Pipe 9 4 3 Air Purging and Refrigerant Charge 11 4 4 Electric Wi...

Page 6: ...10 Never short circuit or cancel the pressure switch to prevent unit damage 11 Please firstly connect the wired controller before energization otherwise wired controller can not be used 12 Before usi...

Page 7: ...es 2 We are not responsible of personal injury or equipment damage caused by improper installation and commission unnecessary service and incapable of following the rules and instructions listed in th...

Page 8: ...n be realized V arious product lineup is provided with capacity range from 30KBtu to 42KBtu which can be widely used in boarding house and working area and especially applicable to the place with vari...

Page 9: ...ce the outdoor unit is turned off Table 1 Energy Level and Capacity Code of the Indoor Indoor unit Model Capacity Code Outdoor unit Wall mounted Lomo 16 GWH09QB D3DNA5E I 09 FGH 42ES MZ GWH12QC D3DNA5...

Page 10: ...ore outgoing 2 The parameters below are tested under rated working condition If there is any change to them please refer to the nameplate 3 The parameters of heating capacity of indoor unit for heat p...

Page 11: ...tall the unit at a place where is against dust typhoon and earthquake 3 Try to keep the unit away from combustible inflammable and corrosive gas or exhaust gas 4 Leave some space for heat exchanging a...

Page 12: ...Liquid Gas Max Pipe length ft Unit and Outdoor Unit ft FGH 42ES MZ 1 4 3 8 246 1 NOTICE 1 When the outdoor unit is above maximum height difference between indoor and outdoor units is up to 49 2ft Whe...

Page 13: ...8 MZ series 4 Installation Instruction 4 1 Outline and dimension of the outdoor unit FGH 42ES MZ Outline dimension and Mounting holes Fig 5 40 42 1 2 24 5 6 17 1 3 14 1 4 15 3 4 43 3 7 Unit inch...

Page 14: ...efrigerant pipe never pull any joints of the indoor unit by force otherwise the capillary pipe or other pipe may crack which then would result in leakage 2 The refrigerant pipe should be supported by...

Page 15: ...stic tape in order to prevent condensation and water leakage 2 The joints of the indoor unit should be wrapped with the insulating material and no gap is allowed on the joint of the indoor unit as sho...

Page 16: ...ing 1 The refrigerant has been charged into the outdoor unit before shipment while additional refrigerant still need be charged into the refrigerant pipe during the field installation 2 Check if the l...

Page 17: ...ir conditioning can be used 3 Do not pull the power cord by force 4 The electric installation should be carried out by the technician as instructed by the local laws regulations and also this manual 5...

Page 18: ...t well according to the instruction 3 The electric installation should be carried out by the technician as instructed by the local laws regulations and also this manual 4 The installation location sho...

Page 19: ...st It may cause insufficient cooling heating capacity Is the unit get proper thermal insulation It may causecondensation and dripping Does the unit drain well It may causecondensation and dripping Is...

Page 20: ...own out again NOTICE If problem can not be solved after checking the above items please contact service center and show phenomena and models Following circumstance are not malfunction Table 11 Malfunc...

Page 21: ...t of outdoor unit indoor fault indicator will flash and conflict will be shown on the wired controller after 5 minutes Indoor unit stops to run and meanwhile change outdoor operating mode as the same...

Page 22: ...3 times Outdoor ambient sensor malfunction Flash 6 times Outdoor tube sensor malfunction Flash 5 times Exhaust sensor malfunction Flash 7 times Attain the temperature of switch on Flash 8 times Freque...

Page 23: ...mote wireless controller has been replaced 4 Check if the filter screen has been set soundly 5 After long period of shutdown open the main power switch 8 hours before re operating the unit so as to pr...

Page 24: ...ency designated by us Warranty should meet the following requirements 1 First run of the unit should be operated by professional personnel from appointed service center 2 Only our manufactured accesso...

Page 25: ...20...

Reviews: