![Ford F2E300R991 Operator'S Manual Download Page 13](http://html1.mh-extra.com/html/ford/f2e300r991/f2e300r991_operators-manual_2318750013.webp)
ASSEMBLY
13
•
Only operate generator on a level surface.
•
Always connect the nut and ground terminal on the frame to an appropriate ground source.
WARNING!
Generator must be properly grounded to prevent electrocution.
•
Place generator on a level surface. All electrical loads
MUST
be disconnected from generator.
•
Turn fuel valve to the “ON” position. (See fig 9)
•
•
For manual start, turn the engine ON/OFF switch to the “ON” position. Pull the recoil handle (starter cord) slowly
until resistance is felt, then pull rapidly. (See fig 11)
•
Let engine run for several seconds and then gradually, as engine warms up, slide the choke lever towards the “RUN”
position until the choke is fully slid to the “RUN” position. (See fig 12)
How to Start Engine (See fig 9-12)
Slide the choke lever to the “Choke” position. (See fig 10)
SKIP THIS IF THE ENGINE IS WARM OR HOT.
Fig 9
Fig 11 Recoil Start
Fig 12
CHOKE
RUN
CHOKE LEVER
CHOKE
RUN
CHOKE LEVER
W AIT
5sec
Fig 10
SKIP THIS IF THE ENGINE IS WARM OR HOT.
The ground terminal located on the back of the generator frame must always be used
to connect generator to a driven ground rod. Connect the ground terminal to the driven
ground rod with a No 8 AWG (American Wire Gauge) copper wire. The wire connects
to the terminal between the lock washer and nut. Tighten the nut securely to ensure
proper connection. Grounding the generator protects you from electric shock that
results from a build up of static electricity or undetected ground faults.
Fig 8
Grounding the Generator (See fig 8)
Summary of Contents for F2E300R991
Page 24: ...DIAGRAMS 24...