6. Serial / LAN Command Control
Up to 20 external devices can be connected to an MFR Main Unit (including MFR-GPI serial ports)
through LAN or serial interface.
6-1. Serial Interface
Crosspoint switchover and tally output can be controlled via the SERIAL ports on the MFR Series
main unit or MFR GPI.
6-2. LAN Interface
The MFR Series main unit is able to connect to a third-party automatic control system via the RJ-45
port (PC-LAN port). The TCP/IP communication protocol is supported. The control PC will be the
Client, and the MFR Series main unit will be the Server.
Basic specifications
Item
Description
IP address (PC-LAN port)
Primary LAN (PC-LAN CPU1) default IP address: 192.168.0.12
Secondary LAN (PC-LAN CPU2) default IP address: 192.168.0.13*
(Subnet Mask: 255.255.255.0)
Port number
Setting range: 49152 to 65534 (default: 23)
Number of PCs
Max. 16
Response / Resend
Wait before sending next command (Resend if the Echo is not
returned.)
Login password
None
Communication protocol
TCP/IP, Control PC: Client, MFR-4000: Server
Crosspoint Remote Control using ASCII code.
Command protocol
Crosspoint Remote Control protocol
* When a redundant CPU is configured, a client should connect to both LAN ports (PC-LAN CPU1 and
PC-LAN CPU2) and send commands to the ports respectively. When the system functions normally, the
secondary port (PC-LAN CPU2) do not respond to commands. But if an error occurs in the CPU1
system, the secondary port will take over the primary port and respond to commands.
Hub
Client
No.1
Client
No.2
Client
No.**
Web-based
Control
PC-LAN port
Server
MFR-4000