33
0 means disabled, 1 means enabled
Default 0xFFFF
0x0B14
2836
Channel 17~24 current
channel switch setting
Unsigned
short
bit0:Represents the switch setting for
channel 7
bit7:Represents the switch setting for
channel 24
0 means disabled, 1 means enabled
Default 0xFFFF
W/R
0x0B15
2837
External power
management time setting
Unsigned
short
Unit M (min), default 120 minutes. When
the photovoltaic power supply stops, the
host can be powered by external 24
power sources, and the power supply
time can be set.
W/R
0x0B16
2838
Current UI display,
direction, reverse order
control
Unsigned
short
Bit0 ~ bit1: Y-axis scale setting of UI
interface
0 means the UI interface displays the
current up to 10A
1 means the UI interface displays the
current up to 20A
2 means the UI interface displays a
maximum current of 30A
bit2: current channel forward / reverse
sequence setting
(Positive sequence: 1 ~ 24 channels
arranged near the host Hall;
Reverse order: Calculate from 24 to 1
channel near the host Hall)
0 means positive order; 1 means reverse
order
bit3: Channel current direction setting
0 means the direction is positive, 1 means
the current is reversed.
0x0000 by default;
W/R
0x0B17
2839
reserved
0x0B20
2848
Alarm function
management 1
Unsigned
short
Bit0 Bus arc,
bit1 Channel arc,
bit2 Low pressure,
bit3 Over pressure,
bit4 High temperature 1,
bit5 High temperature 2,
bit6 Channel current value is reversed,
bit7 Reverse total current is high,
bit9 The total current is high,
bit10 Channel current value is zero,
W/R