background image

REF12  LB 

 

11

 

§

Temperature Log – to display a chronological listing of logged 
temperatures (latest logged temperature will display first), touch the 
Temperature Log label to the left of the screen . Use the UP and 
DOWN arrows to the right of the screen to scroll through the logged 
temperatures .

Fig. 15

38.4

 

F

HIGH

LOW

P3

P1

41.5 F

35.1 F

(1 - 10)

ON

3

OFF

Advanced Settings

i

i

20130101

20130201

+ Zoom in

-  Zoom out

Options

Event log

Temperature log

3/1/13 

12:30AM 

41.1F 

41.0F

3/1/13 

01:00AM 

39.4F 

39.8F

Date

3/1/13 

12:15AM 

42.2F 

41.1F

3/1/13 

12:45AM 

40.3F 

39.9F

3/1/13 

01:30AM 

38.6F 

39.7F

3/1/13 

01:15AM 

38.5F 

39.8F

3/1/13 

01:45AM 

39.7F 

39.8F

3/1/13 

02:00AM 

39.8F 

39.9F

3/1/13 

02:30AM 

40.0F 

39.7F

3/1/13 

02:15AM 

39.9F 

39.8F

3/1/13 

03:00AM 

41.8F 

39.5F

3/1/13 

02:45AM 

41.9F 

39.6F

3/1/13 

03:15AM 

40.7F 

39.6F

3/1/13 

03:30AM 

40.0F 

39.7F

3/1/13 

04:00AM 

41.9F 

39.9F

3/1/13 

03:45AM 

41.7F 

39.8F

3/1/13 

04:30AM 

40.5F 

39.7F

3/1/13 

04:15AM 

40.4F 

39.6F

3/1/13 

04:45AM 

42.0F 

39.8F

3/1/13 

05:00AM 

41.9F 

39.9F

3/1/13 

05:30AM 

41.7F 

39.7F

3/1/13 

05:15AM 

41.8F 

39.6F

3/1/13 

06:00AM 

40.8F 

39.9F

3/1/13 

03:45AM 

40.7F 

39.8F

3/1/13 

03:15AM 

40.9F 

39.6F

Time

Product

RTD 1

+ Zoom in

-  Zoom out

Options

Event log

Temperature log

 

§

Event Log – to display a chronological listing of events (including errors, 
alarms and alerts), touch the 

Event Log label to the left of the screen . 

Use the 

UP and DOWN arrows to the right of the screen to scroll 

through the logged temperatures .

Fig. 16

38.4

 

F

HIGH

LOW

P3

P1

41.5 F

35.1 F

(1 - 10)

ON

3

OFF

Advanced Settings

i

i

20130101

20130201

+ Zoom in

-  Zoom out

Options

Event log

Temperature log

 

Verified 

2:30PM 

20130116

Event

Description

Time

Date

+ Zoom in

-  Zoom out

Options

Error  

Out of temperature 

2:28PM 

20130116

  

Back in temperature 

2:35PM 

20130116

Alert  

Door open 

4:55PM 

20130116

 

Verified 

5:05PM 

20130116

 

Door closed 

4:56PM 

20130116

 

Power restored 

7:10PM 

20130116

 

Verified 

7:20PM 

20130116

Error  

Door open alarm 

5:00PM 

20130116

 

Verified 

2:30PM 

20130116

Error  

Out of temperature 

2:28PM 

20130116

  

Back in temperature 

2:35PM 

20130116

Error  

Power failure 

7:00PM 

20130116

Temperature log

Graph

Data logging 

 

§

The controller is capable of storing up to 50,000 readings per probe . 
The factory setting for the sample rate is every 15 minutes, which will 
provide enough storage for 520 days . The sample rate can be change 
to provide data logging for a longer or shorter time interval by changing 
the 

Sample Rate (Min) in the advanced settings menu .  0 = off and 

360 minutes maximum .

Data Storage

 

§

Data can be captured different ways . The factory default is for the data 
to overwrite itself when the memory is full . This can be changed in the 
advanced setting under 

Data storage overwrite . When this parameter 

is set to 

No, the system will display an alert when the memory is 75% 

full . To clear the alert the data must be downloaded . 

Data duration alarm

 

§

A reminder can be set to download the data in the 

Data duration alarm 

in the advanced setting . The data duration can be set from 

1 to 180 

days . If the data duration alarm is used, then the Alarm on data full 
parameter in the advanced setting must also be set to 

Yes .

Summary of Contents for REF 12-LB Series

Page 1: ...rder parts online www follettice com 01324227R00 H E A LT H C A R E TM 801 Church Lane Easton PA 18040 USA Toll free 877 612 5086 1 610 252 7301 www follettice com healthcare Following installation pl...

Page 2: ...ll product bottle 6 Power the Unit 6 Controller Operation 6 Use and care of the LCD touchscreen 6 Cleaning 18 Interior cleaning 18 Exterior cleaning 18 Annual cleaning 18 Refrigeration System 18 Defro...

Page 3: ...numbers are designed to provide information about the type of refrigerator you are receiving Following is an explanation of the different item numbers Model Cubic foot capacity 12 Configuration LB La...

Page 4: ...D resistance temperature device Ambients Intended for indoor use where ambient temperature measured at the condenser inlet does not exceed 80 F 27 C and ambient relative humidity does not exceed 60 RH...

Page 5: ...ecuted in conditions other than those specified herewith The equipment is secured to a wooden pallet base wrapped in a plastic film and packaged into a three waves carton box The equipment must be han...

Page 6: ...ight hand corner Press lower left corner of front facade door to access power switch inside Controller Operation Use and care of the LCD touchscreen The LCD touchscreen utilizes capacitive touch techn...

Page 7: ...n the upper right corner The high low temperatures will appear below the temperature display To the left of the high low temperature a time and date stamp will be displayed View the bottom probe tempe...

Page 8: ...hide the temperature after 0 600 seconds of inactivity touch the box to the right of the delay 0 600 box Use keypad or UP and DOWN arrows to select from 0 600 Temperature F C Toggle between F and C t...

Page 9: ...rm Delay Power Alarm This unit is equipped with a Power Alarm that will sound if the unit loses power for more than five minutes The Power Loss Alarm box will display every five minutes then the scree...

Page 10: ...te or the temperature When the screen is touched or the unit has an alarm or event it will return to the home screen The screen saver can be changed in the advanced setting Screen saver function blank...

Page 11: ...4F HIGH LOW P3 P1 41 5 F 35 1 F 1 10 ON 3 OFF Advanced Settings i i 20130101 20130201 Zoom in Zoom out Options Event log Temperature log Verified 2 30PM 20130116 Event Description Time Date Zoom in Z...

Page 12: ...equired to download data for a certain time period you can set a download data reminder on the Performance Plus unit Download data reminder can be found in the advanced setting under Data duration and...

Page 13: ...e the keypad to enter the time Press to accept or to cancel AM PM touch displayed value to toggle between AM and PM Month touch number displayed and use the keypad to enter the month Press to accept o...

Page 14: ...ide the home screen It will display a blank screen temperature or time and date Screen Saver Timer 0 seconds 0 to 600 seconds Amount of Time before the screen saver initiates Control Setup REF FZR Use...

Page 15: ...arm3 Reset 1 degrees 0 to 10 degrees Temperature difference to reset Alarm 3 General Alarm Reset Alarm Ringback 10 minutes 0 to 120 minutes Defines the time delay until the alarm will resound Alarm Re...

Page 16: ...to a defrost Defrost Control Manual only Power on manual only disable time of day compressor on time Defines tactic for initiating a defrost Graphing X Axis Range hrs 168 hours 1 to 384 hours Time spa...

Page 17: ...enu Viewable Cut In View cut in temperature Cut Out View cut out temperature Probe 1 temp View temperature of probe 1 Probe 2 temp View temperature of probe 2 Probe 4 temp View temperature of probe 4...

Page 18: ...e cleaner Annual cleaning Removal of dust and other particulates from air intake areas and the condenser is important for proper operation Environments with large amounts of dust may require more freq...

Page 19: ...hours of compressor run time the system will initiate a defrost When the defrost cycle is initiated both the evaporator fan and condenser fan cycle off while the compressor continues to run The defros...

Page 20: ...ooling system For instance a unit running at the default set point of 4 4 C 40 F will have the cooling system cut in at 3 3 C 38 F and cut out at 0 3 C 32 6 F according to the P1 Control probe located...

Page 21: ...tions for proper grounding to reduce risk of electrostatic discharge ESD to the controller board 5 Locate the control board stand offs 6 Using Needle nose pliers pinch the stand off tabs and gently pu...

Page 22: ...lace 4 Open and close door checking for proper gasket seal without pinching against refrigerator Modular Refrigeration System Follett s Modular Refrigeration System system allows technicians to remove...

Page 23: ...REF12 LB 23 Wiring diagram...

Page 24: ...4 Temperature probe control and defrost 01310564 5 Condenser coil with drier 01311901 6 Condenser fan motor 01311885 7 Compressor with start components and drier 01311943 8 Cap tube and filter drier...

Page 25: ...oor assembly left hand 01313105 8 Solid door stainless steel right hand only 01313097 9 Gasket for solid door 01310614 10 Spring kit bottom hinge solid door 01310580 10 Spring kit bottom hinge glass d...

Page 26: ...mpressor defrost 01312560 8 LED driver glass door only 01316108 9 Battery charger 01316041 Not shown Temperature probe bottle 01089614 Not shown Harness control to touchscreen 01064856 Not shown Probe...

Page 27: ...REF12 LB 27...

Page 28: ...rant a y evaluaci n del equipo son importantes para que podamos realizar un seguimiento de nuestro equipo y registrar el rendimiento de la maquinaria Por favor registre las garant as del equipo Follet...

Reviews: