c) Chimney requirement:
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING
ANOTHER APPLIANCE!
Agorafocus 850 requirement: the total length of flue (inside + outside) must
be 13 feet minimum (16 feet for an installation less than 3 miles from the
ocean or if a 30° elbow is necessary).
The agorafocus 850 must be connected to a chimney complying with the
requirements for Type HT chimneys in the standard for Chimneys, Factory-
built, Residential Type and Building Heating Appliance, UL 103. For example,
a class A insulated stainless steel flue chimney system with an 10-inch
minimum inside diameter.
d) Structural requirement:
CAUTION: THE SUPPORT OF THE ANCHOR PLATE (ROOF
STRUCTURE, SLAB, ETC.) OR PEDESTAL (FLOOR, SLAB, ETC…) MUST
BE SIZED IN CONGRUENCE WITH THE FIREPLACE STATIC AND
DYNAMIC CHARGES. THE SIZE CALCULATION FOR THE SUPPORT IS
NOT THE RESPONSIBILITY OF FOCUS OR ITS AFFILIATES. IT IS YOUR
RESPONSIBILITY TO CONSULT WITH AN ENGINEER OR ARCHITECT
FOR YOUR PROJECT.
e) Connector:
Connectors are all non-insulated chimney parts including focus black flue,
focus 10" universal adaptor and the chimney manufacturer single wall slip
connector.
To avoid heat traps the chimney connector shall not pass through an attic or
roof space, closet or similar concealed space, or a floor, or ceiling.
Passage through an attic, roof frame floor, or ceiling must be done using an
insulated chimney respecting all chimney manufacturer clearances.