background image

TESTING AND COMMISSIONING

Turn on and test the gas supply up to the fire for any leaks, in accordance with the current edition of BS 6891
(natural gas installations) or the current edition of BS 5482 pt1 (propane installations).

OPERATING THE APPLIANCE

The pilot is visible behind the left hand side of the burner.

The control knob is located on the lower right hand side of the outer
case. It is of a spherical design and is marked as shown in the diagram
to the right;

Push in and turn the control knob to the SPARK position, and hold
there for a few seconds. Continue turning anti-clockwise through the
spark click to the PILOT light position, ensuring the pilot has lit. If not,
return the knob clockwise, and repeat.

When the pilot lights after the spark, keep the knob depressed for
approximately ten seconds. Now release the knob and the pilot
should stay alight. If the pilot is extinguished during use, wait three
minutes before repeating the ignition procedure. 

To achieve the HIGH setting, push the control knob in slightly and continue turning anti-clockwise to the high
position. The main burner should light after a few seconds.  To decrease the setting to LOW, turn the control
knob clockwise to the low setting.

To turn to the PILOT position from the HIGH or LOW positions, press the control knob in, and return to the pilot
position and release. To turn the fire OFF, keep the knob pressed in, return to the off position and release.

SPARK FAILURE 

The gap between the spark electrode and the pilot should be 3 - 5mm to produce a good spark.  There should
be no need to adjust this.  If under any circumstances the piezo electric spark fails, the pilot cannot be lit man-
ually.

SETTING PRESSURE

The pressure test point is located on the left hand side of the appliance, on the main burner pipe, next to the
brass restrictor/connector. Release the setting pressure test point screw, and attach a U gauge. Light the fire on
the HIGH setting.

To commission the appliance, the burner pressure must be in accordance with the figures stated in the data sec-
tion of these instructions. 

The fire is factory set to achieve these pressures and any
significant variation could indicate a supply problem. If
the pressure is too high, the gas supply meter/regulator
may be set incorrectly.  This should be checked with the
fire running and if necessary reset by the gas supplier.

If the burner pressure is too low, then check the inlet
pressure with the appliance running.  If this is less than the
inlet pressure stated in section 2.0 of these instructions it
will need to be reset by the gas supplier. If the setting pres-
sure is too low, but the meter pressure is acceptable, then a
problem in the supply pipework is to be suspected. 
This will be dirt and debris, kinked or inadequate size
pipes, restriction in a fitting, shut off elbow not fully open or solder flashing across a joint. Identify the cause of
the restriction and rectify. Switch the fire off, disconnect the U gauge and refit the test nipple screw. Light the
fire and check for gas soundness. 

In the event that the burner pressure is not in accordance with the figures stated in the data section of these
instructions, the appliance must not be commissioned, and the manufacturer should be contacted for guidance.

6

8.3

8.0

8.1

8.2

‘OFF’ position

‘SPARK’ position

‘LOW’ position

‘HIGH’ position

©

2008 Focal Point Fires plc.

Summary of Contents for MEMOIRS

Page 1: ...safekeeping Revision B 10 08 Country s of destination GB IE PINOIR MEMOIRS REFLECTION SATURN WALL MOUNTED HIGH EFFICIENCY GAS FIRE Focal Point Fires plc Christchurch Dorset BH23 2BT Tel 01202 499330...

Page 2: ...he text images and layout of this booklet is owned by Focal Point Fires plc You are not per mitted to copy or adapt any of the content without the prior written permission of Focal Point Fires plc The...

Page 3: ...moke candle smoke etc exist may cause the walls to become discoloured This appliance is intended as a secondary source of heat only and should not be used in a room without some form of background hea...

Page 4: ...igned to be wall hung Do not recess any part of the appliance into the wall This appliance may be installed in any room in the home except bathrooms or bedrooms Installation in living rooms is common...

Page 5: ...appliance are able to withstand prolonged exposure to moderate heat and moisture before proceeding with their installation The back of the appliance may be installed directly onto a combustible wall...

Page 6: ...s supply pipework to enter the appliance firebox These entry points are knock out type holes Select the most appropriate entry point and knock out the relevant hole The positions of these holes are sh...

Page 7: ...on of IGE UP 7 Using the fitting template provided mark the fixing positions on the wall Pinoir Memoir and Reflection models Mark the positions shown as L40 fixing points Saturn models Mark the Positi...

Page 8: ...his If under any circumstances the piezo electric spark fails the pilot cannot be lit man ually SETTING PRESSURE The pressure test point is located on the left hand side of the appliance on the main b...

Page 9: ...he appliance and the need for regular servicing Frequency of service depends on usage but MUST be carried out at least once annually Advise that cleaning of the fire maybe achieved when the fire is co...

Page 10: ...sary is to ensure the spark gap is correct See specifications for gas setting NEVER MODIFY OR BEND THE THERMOCOUPLE TO MAKE THE PILOT STAY ALIGHT If the pilot will not stay lit there is a problem with...

Page 11: ...ay lit there is a problem with dirt the gas supply or the thermocouple needs replacement Modifications are dangerous and can have a serious unseen effect on safety NEVER MODIFY OR BEND THE THERMOCOUPL...

Page 12: ...this appliance considers all surfaces as working surfaces with the exception of the control knob and control panel Combustible items such as flooring and furniture and soft wall coverings such as blo...

Page 13: ...ished that any mirrors or picture frames etc to be positioned on the wall above the appli ance are able to withstand prolonged exposure to moderate heat and moisture before proceeding with their insta...

Page 14: ...ous section If pilot disturbance is not the cause then the ODS safety system may be in operation Switch the appliance OFF call in your installer to check the appliance and ventilation Remedial work mu...

Reviews: