User Manual: 5 Gallon Smart Foam Unit | English

READ ALL INSTRUCTIONS BEFORE OPERATING EQUIPMENT

 Model No.: FI-5N-SM, FI-5NK-SM, FI-5NV-SM AND RELATED UNITS

Troubleshooting Instructions:

• 

Check to ensure that the discharge hose is uncoiled 

properly, and that there are no kinks that could obstruct 

fluid flow.

• 

Check the suction line and strainer for debris or damage. 

Clean or replace as needed. To prevent damage to the 

unit, the strainer (STR38-IL) must always be used.

• 

Check the air regulator bowl (ABR25) and air filter (AFR25) 

for debris such as water, oil, or rust particles.  Clean by 

unthreading the air regulator bowl (ABR25) from the air 

regulator (R25).

• 

If the needle valve (NV14Y) is open too far, the pump 

(P56/P56K/P56V) may cycle improperly due to lack of air 

pressure.  If this occurs, close and readjust the needle 

valve (NV14Y) as described in the Operation Instructions.

• 

Make sure proper foaming chemical and concentration 

are being used.

• 

If air passes through the pump (P56/P56K/P56V) without 

cycling, the pump needs to be replaced.

• 

If solution backs up into the air regulator bowl (ABR25), 

the check valve (CV38) needs to be replaced.

• 

If foam comes out wet, no matter where the needle valve 

(NV14Y) is positioned, the check valve (CV38) may need to 

be replaced.

• 

Check for proper air pressure on the air gauge (AG100).  

The air regulator (R25) is factory set at 50 psi (3.4 bar).  

Operating range is 40 to 80 psi (3 to 5 bar) with 5 to 10 

CFM (141.6 to 283.3 l/min).

• 

If the unit operates at a reduced pressure:

1.  Check the air compressor supplying the unit. If the 

pressure is less than 40 psi, turn the unit off until the 

compressor can catch up.

2.  If the air supply is 50 psi (3.4 bar) or above, check 

the air gauge (AG100), which should read near 50 psi 

(3.4 bar). If the air gauge reads more or less than 50 

psi (3.4 bar), adjust the pressure by turning the knob 

on the top of the air regulator (R25).

3.  If the problem persists, the stainless steel mixing 

mesh (SS-MESH) inside the tee fitting (SST12HB38) 

could be plugged.  Remove and clean the mesh 

following the instructions below: 

a.  Ensure that the unit has been flushed and 

disconnected from the air supply according to 

the “After Use Instructions.”  Also ensure that 

the unit tank is empty, and/or that the valve 

(PVCV34FM) at the base of the suction line is 

closed.

b.  Remove the stainless hose barb (HBSS1258) 

from the tee fitting (SST12HB38).

c.  The stainless steel mixing mesh (SS-MESH) 

is located inside the tee fitting (SST12HB38).  

Remove the old mesh and the screen that 

holds it in place.  If the mesh and screen are 

in good condition, they can be cleaned and 

re-used.  If not, they should be replaced with 

new parts.

d.  Insert the new mesh (SS-MESH).

e.  Insert the new screen (SSST).  Make sure it is 

seated securely, but not bent or deformed.

f.  Reconnect the hose barb (HBSS1258) to the 

tee fitting (SST12HB38). Attach the 5/8 inch 

hose to the hose barb (HBSS1258) and secure 

it with the screw band clamp (SSC58).

g.  If you found a lot of particles or blockages 

inside the mesh, check the suction line 

strainer (STR38-IL) to make sure it is in place 

and operating correctly.

• 

If the unit activates when the air trigger port is not 

covered:

1.  Verify that the air trigger port is clean and free of 

blockages or debris, and the discharge hose is not 

kinked or obstructed.

2.  If the problem persists, try bypassing the air trigger. 

To do this, disconnect the 1/4 inch hose from 

the wand. Point the wand in a safe direction and 

connect an air line to the unit. Then, use your thumb 

or finger to seal the open port of the 1/4 inch hose 

at the wand. 

a.  If the unit activates when you connect the air 

line, the valve block (SM-PV) may need to be 

replaced. 

b.  If the unit does not activate when you 

connect the air line, the hose or wand 

assembly may need to be replaced.

• 

If the unit does not activate when the air trigger port is 

covered:

1.  Confirm the incoming air supply is consistently 50 psi 

(3.4 bar) on the air guage (AG100). 

2.  If the problem persists, the valve block (SM-PV) may 

need to be replaced.

Summary of Contents for FI-5N-SM

Page 1: ...USER MANUAL MODEL NUMBER FI 5N SM FI 5NK SM FI 5NV SM AND RELATED UNITS 5 Gallon Smart Foam Unit English Original Instructions ...

Page 2: ...lways keep the discharge hose free of kinks or obstructions Always rinse and drain unit after use as described in the After Use Instructions Always store unit disconnected from the compressed air source Do not exceed an incoming air pressure of 100 psi 7 bar Do not exceed a fluid temperature of 100 F 37 C Always flush the unit with fresh water for 5 minutes when switching from an alkaline to an ac...

Page 3: ...e Compressed air Chemical pickup type Draws from pre mixed solution Number of products unit can draw from One product Capacity 5 gallons 22 02 liters Discharge hose diameter length 20 ft 9 1 m bonded hose with 5 8 in 15 9 mm and 1 4 in 6 4 mm inside diameter Discharge wand tip type Ultra high molecular weight UHMW polyethylene handle and wand extension with 65 fan tip and built in zero tip Output ...

Page 4: ...ut off and depressurize Foam that is already in the discharge hose may seep out but no more foam will be created until you cover the air trigger again After Use Instructions 7 Rinse the unit tank thoroughly with fresh water Then fill the tank with fresh water 8 Activate the unit and allow it to run for 2 4 minutes or until all chemical has been flushed from the system 9 Disconnect the air line fro...

Page 5: ... problem persists the stainless steel mixing mesh SS MESH inside the tee fitting SST12HB38 could be plugged Remove and clean the mesh following the instructions below a Ensure that the unit has been flushed and disconnected from the air supply according to the After Use Instructions Also ensure that the unit tank is empty and or that the valve PVCV34FM at the base of the suction line is closed b R...

Page 6: ...RE OPERATING EQUIPMENT Model No FI 5N SM FI 5NK SM FI 5NV SM AND RELATED UNITS TANK 5N TANK 5N HNDL CST5 WHL JC35B TANK ASSEMBLY ITEM NUMBER TANK 5N A SSC58 SSC14 HBSS1258 HBSS1814 SMH Air Trigger Port PW1238 ST65150SS WAND ASSEMBLY ITEM NUMBER SMWA DISCHARGE HOSE ASSEMBLY ITEM NUMBER H5814 20 ...

Page 7: ...SM AND RELATED UNITS H38B H SST12HB38 SSC38 P56 P56K or P56V P56 BRKT P56 BRKT SCREW NV14Y AG100 R25 BPS 58SO BPS SSR SN1414 HBSSEL1438 P18 HBSSEL1438 H14B H CV38 Available per Available per HBBEL1414 HBSSEL1438 SM PV EC14 2 HBSS1438 BACK PLATE ITEM NUMBER PA PF SM HBSS1414 HBSS1258 FWP12 FWLG14 SSA14 TW916 BPS 58S0 AP25 NV14Y BACK PLATE Outside View ...

Page 8: ...S P56 PUMP WITH SANTOPRENE SEALS INCLUDES HOSE BARBS AIR FITTING AND EXHAUST BARB P56K PUMP WITH KALREZ SEALS INCLUDES HOSE BARBS AIR FITTING AND EXHAUST BARB P56V PUMP WITH VITON SEALS INCLUDES HOSE BARBS AIR FITTING AND EXHAUST BARB P56 BRKT PUMP BRACKET STAINLESS STEEL P56 BRKT SCREW HI LO SCREW FOR RETAINING P56 BRKT PLPF PORTABLE FOAMER BACK PLATE W HINGE AND HOLES PLPF PIN 302 STAINLESS PORT...

Reviews: