FNW FIGURE 751 Installation, Operation & Maintenance Instructions Manual Download Page 4

DUCTILE IRON FLANGED GATE VALVE

FIGURE 751

FNW.COM

We reserve the right to modify or improve the designs or 

specifications of our products at any time without notice.

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

©2022 Ferguson Enterprises, LLC 0522 4108704

TROUBLESHOOTING

Problem

Possible Causes

Remedy

Bonnet nuts are loose

Tighten to values listed in Table 2

Leakage from 

the bonnet

Bonnet sealing gasket

is damaged

Disassemble valve and install a new gasket

Bonnet flange faces

are damaged

Repair damaged area and install a new gasket

 

Valve is not properly seated

Check with hand wheel to see if the valve is tightly closed

Leakage past

the seat

There is an obstruction 

between the seat and disc

Open and close the valve a couple times 

to see if the obstruction clears

Disc is damaged or worn

Disassemble the valve, inspect

internal components, and repair or replace as required

INSPECTION

Valve components are subject to normal wear and 

tear and must be inspected and replaced as needed. 

The frequency of inspection and maintenance depends on the severity 

of the conditions of use.

Table 2

 Tightening values

Size

Torque-Bolts between

bonnet and body (NM)

2.5"

65

3"

70

4"

70

6"

80

8"

100

10"

100

Summary of Contents for FIGURE 751

Page 1: ...ction to ensure that there is no water accumulation on or in the valve The valve comes with a protective end cap to prevent mechanical damage and prevent the intrusion of dust and foreign objects If a...

Page 2: ...er the valve is installed re check all the bolts and nuts of the connecting flanges and re tighten them if they are found to be loose OPERATION Gate valves are not designed for throttling modulating s...

Page 3: ...tightend Inadequate amount of packing rings Install additonal packing rings Packing is hard and dry Replace with new packing Leakage through the stem packing Packing was not properly cut and staggered...

Page 4: ...Repair damaged area and install a new gasket Valve is not properly seated Check with hand wheel to see if the valve is tightly closed Leakage past the seat There is an obstruction between the seat and...

Page 5: ...in the operation section Intermediate positioning is not recommended If necessary immediately tighten any loose bolts and grease around the valve stem PERIODIC INSPECTION Valves should be inspected p...

Page 6: ...e or other foreign matter Wipe disc 4 with a cloth Clean body 5 and bonnet 2 inside and outside surfaces and all nuts and bolts Put packing 3 into the packing groove of bonnet 2 align and center the p...

Page 7: ...e valve stem with a cloth soaked in solvent Count the original number of packing rings If replacing with new packing use a sharp tool to cut each ring at a 45 angle see Figure 2 stagger adjacent packi...

Page 8: ...E DEFECTIVE PRODUCT S PURCHASED DURING THE PREVIOUS CONTRACT YEAR Labor Allowance Seller makes NO ADDITIONAL ALLOWANCE FOR THE LABOR OR EXPENSE OF REPAIRING OR REPLACING DEFECTIVE PRODUCTS OR WORKMANS...

Reviews: