Connecting communication port (if it is necessary)
3.2.1 Device’s installation flow chat illustrated as following
3.2.2 Environment Requirement
Item
Requir ement
Machine hall spac e
W hen us er install mac hine frame array in one
machine hall, the distanc e between 2 row of
machine frames should be 1.2~1.5m and the
distanc e to wall should be no less than 0.8m
。
Machine hall floor
Electric Is olation, D ust Free
Volume
rec eptivity
of
ground
anti-static
material:1
×
10
7
~1
×
10
10
Ω
,Grounding
current
limiting resistanc e: 1M
Ω
。
Floor bearing should be greater than 450Kg/m
2
。
Environment
temperature
5~40
°
C sustainable
,
0~45
°
C short time
installing air-c onditioning is rec ommended
Relative H umidity
20%~80% sustainable 10%~90% short time
Pressure
86~105KPa
Door & window
Installing rubber strip f or s ealing door-gaps and
dual level glass es f or window
W all
It c an be c overed with wallpaper, or bright less
paint.
Fire protection
Fire alarm s ystem and extinguisher
Power
Requiring devic e power, air-c onditioning power
and lighting power are independent to eac h
other. D evic e power requires AC power 220V
50H z. Pleas e c arefully check bef ore running.
3.2.3 Grounding Requirement