Operating manual EMGZ308
11
Gain and offset with fixed setting
If the signal is processed by a control unit
(i.e. a PLC), configuration with fixed gain
and offset is recommended (offset = 0;
gain = 1111). Therefore, the jumpers have
to be set according to fig. 8. With this
configuration, the good thermal
characteristics of the hybrid module are
best utilized. The output signal will be
20mA when the nominal force of the
sensor is applied.
7.3 Configuring the output
Each channel provides a voltage output (±10V) and a current output (0...20mA or
4...20mA) which are active simultaneously. The signal of the current output is configured
as follows:
Current output 0...20mA
The jumpers have to be set according to
fig. 9. This is the standard FMS factory
setting.
Current output 4...20mA
The jumpers have to be set according to
fig. 10.
fig. 8: Jumper setting for fixed gain
and offset
E308010b
fig. 9: Jumper setting for current
output 0...20mA
E308010c
fig. 10: Jumper setting for current
output 4...20mA
E308010d