Operating manual EMGZ307
15
8
Trouble shooting
Error
Cause
Corrective action
Output shows signal > 0
although material has
no tension
Offset setting is bad
Readjust offset (refer to „7.5
Calibrating the measuring
amplifier“)
Current output is
configured for
4...20mA
Change jumper setting if required
Output signal is not
stable although material
tension doesn’t change
Cut-off frequency too
high
Adjust cut-off frequency (refer to
„7.4 Configuring the lowpass filter“)
Ground terminal of
the output isn’t 0V
Connect Gnd terminal of the output
(terminal 8) with earth
Adjusting the trimmers
causes no result
Jumpers are not set to
„infinite“
Set jumpers to „infinite“
Output shows no
reaction, or 1 or 2
LED’s don’t light
Fuse blown
Replace fuse on power supply
Power supply not
correct
Check / correct power supply
Measuring amplifier
defect
Contact FMS customer service
9
Technical Specification
Sensor excitation
5VDC ±20ppm/K max. 30mA [±11ppm/°F]
Gain factor range
fixed: 1111; variable: 500...5000
Offset range
fixed: 0mV; variable: ±9mV
Temperature drift offset fixed: < 20ppm/K [11ppm/°F]; variable: ca. 50ppm/K
[28ppm/°F]
Linearity error
< 0.1%
Tension output
±10V min. 1000
Ω
Current output
0/4...20mA max. 500
Ω
Lowpass cut-off
frequency
adjustable, ca. 1...1000Hz
Power supply
24VDC (18...36VDC) max. 0.1A
Power consumption
max. 2.5W
Temperature range
–10...+60°C [14...140°F]
Protection class
IP67