FMI V300 Setup Instructions Download Page 3

display.  The stroke rate is displayed as a percentage
of the fastest rate.  If you attempt to go beyond these
limits, the display will show three dashes indicating you
have reached a limit.  

To run the V300 system in manual mode, simply turn
the Mode Switch to "MANUAL" using a screwdriver.  
Note: In manual mode, the motor will not start until the
user presses the "RUN" button.  This allows the user to
adjust the stroke rate prior to starting the pump.  The
last stroke rate to be selected before turning off the
power will be the stroke rate stored for the next power
up. 

3.2.2

Analog Input Modes

General Note:

While configured for a remote inter-

face, the actual percentage of the Stroke Rate
Maximum is displayed on the LCD for easy monitoring. 

a) 0-5 Volt Mode:

Use this mode  to remotely control

the stroke rate with a voltage source of 0 to 5 VDC.
This voltage level interface utilizes the "ANALOG
INPUT" connector on the control module to connect to
the user's voltage source. (see figure 2) 

Standard RG58 or other coaxial cable should be uti-
lized for inducted noise immunity.  The 0-5 volt inter-
face requires approximately 2 mA of drive current at 5
volts thus making it compatible with most analog volt-
age interface modules.  The stroke rate is displayed as
a percentage of the fastest rate.  The stroke rate is lim-
ited to a minimum of 5.0% and a maximum of 100.0%.
If the control voltage is less then the minimum of 5.0%
the display will alternate three dashes and the control
value, indicating you are under the limit. 

To run the V300 system in 0-5 V mode, simply turn the
Mode Switch to "0-5 V" using a screwdriver (see Fig 1).

0-5 Volt input specifications:

Isolated input:

limited to ± 30 VDC from 

earth ground. 

Input voltage range 

0-5 VCD

Input current at 5 volts

2 mA

Maximum Rate (100.0%)     4.5 V
Minimum Rate (5.0%)

225 mVDC

Interface Linearity 

1.5%

Accuracy

1%

Caution:

If power is applied to the control unit

while in 0-5 V mode, the motor will start automatically if
the input voltage is 225 mV or above. The "STOP" and
"RUN" buttons will stop and start the pump while in the
0-5 VDC mode however the up down arrows are not
functional in this mode.

b) 0-10 Volt Mode:

Use this mode  to remotely control the stroke rate with

a voltage input source of 0 to 10 VDC. This voltage
level interface utilizes the "ANALOG INPUT" connector
on the control module to connect to the user's voltage
source.  Standard RG58 or other coaxial cable should
be utilized for inducted noise immunity. (See Figure 2
for cable connections)

The 0-10 VDC interface requires approximately 1 mA
of drive current at 10 VDC thus making it compatible
with most analog voltage interface modules.  The
stroke rate is displayed as a percentage of the fastest
rate.  The stroke rate is limited to a minimum of 5.0%
and a maximum of 100.0%.    If the control voltage is
less then the minimum of 5.0% the display will alternate
three dashes and the control value, indicating you are
under the limit. 

To run the V300 system in 0-10 V Mode, simply turn the
Mode Switch to "0-10 V" using a screwdriver. (See
Figure 1) 

0-10 Volt input specifications

Isolated input: 

limited to ± 30 VDC from 

earth ground.

Input voltage range:  

0-10 VDC

Input current at 10 volts:      1 mA
Maximum Rate (100.0%):     9.5 VDC
Minimum Rate (5.0%):  

450 mVDC

Interface Linearity:  

1.5%

Accuracy:  

1%

Caution:

If power is applied to the control unit

while in 0-10 V Mode, the motor will start automatically
if the input voltage is 450 mV or above.  The "STOP"
and "RUN" buttons will stop and start the pump while in
the 0-10 Volt mode however the up down arrows are
not functional in this mode.

c) 4-20 mA Mode:

Use this mode to remotely control

the stroke rate with a current source of 4 to 20 mA DC.
This current level interface utilizes the "ANALOG
INPUT" connector on the control module to connect to
the user's current loop controller.  

Standard RG58 or other coaxial cable should be uti-
lized for inducted noise immunity.  The 4-20 mA inter-
face requires approximately 3.8 V of drive voltage to
achieve 20 mA. thus making it compatible with most
current control loop configurations.  

The input is isolated to allow the control module to be
inserted anywhere into a current loop that does not
exceed ± 30 volts from earth ground.  The stroke rate
is displayed as a percentage of the fastest rate.  The
stroke rate is limited to a minimum of 5.0% and a max-
imum of 100.0%. If the control current results in less
then the minimum of 5.0% the display will alternate
three dashes and the control current percentage, indi-

!

!

IN-V300-08

3

Summary of Contents for V300

Page 1: ...ccur When pulling out cords from outlets do not pull cord grasp plug to prevent plug damage or electrical shock Fluid Metering Inc Drive Motors become HOT and can cause a burn DO NOT TOUCH Turn off the electrical power before checking pump for any problems Connect motor speed controllers or any other electrical devices based on Fluid Metering Inc specifications Any unauthorized work performed on t...

Page 2: ... The system is configured for table top installation ini tially with rubber grommets slid into the mounting slots Before moving on to configuring the control module make sure that these rubber grommets are in place There are no further installation steps for table top use 3 1 2 Wall Mounting For wall mounting it is necessary to remove the four rubber grommets from the control module before attempt...

Page 3: ...Mode Use this mode to remotely control the stroke rate with a voltage input source of 0 to 10 VDC This voltage level interface utilizes the ANALOG INPUT connector on the control module to connect to the user s voltage source Standard RG58 or other coaxial cable should be utilized for inducted noise immunity See Figure 2 for cable connections The 0 10 VDC interface requires approximately 1 mA of dr...

Page 4: ...able to the AC power out let a Do not attempt to apply power to the control unit until all of the above installation and set up procedures have been completed b Double check reversing and mode switches prior to turning on the power switch c Since the pump drive module can be a substantial distance from the control unit it is imperative the operator visually verify that the pump drive module is rea...

Page 5: ...uropean Communities The fuse holder will not open without removing the power cord Once the power cord is removed simply pry up the fuse cover at the indicated screwdriver slots swing open the cover hinged towards the power sock et Then remove the fuse holder block by pulling it straight out exposing the fuses Always replace both fuses with the same type and rating even if only one has blown The V3...

Page 6: ......

Page 7: ...5 75 146 1 4 0 101 6 V300 OUTLINE V300 MOUNTING TEMPLATE Figure 4 ...

Reviews: