INSTALLATION
Continued
If Using Mantel
You must have noncombustible material(s)
above the fireplace opening. Noncombustible
materials (such as slate, marble, tile, etc.) must
be at least 1/2" thick. With sheet metal, you
must have noncombustible material behind it.
Noncombustible material must extend at least
12" up. See Figures 5 and 6 and Figure 7 on
page 11 for minimum clearances.
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required
clearances between fireplace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between
mantel shelf and top of fireplace opening, a
hood is not required (see Figure 6).
Figure 6 - Minimum Mantel Clearances
Without Using Hood
MINIMUM NONCOMBUSTIBLE
MATERIAL CLEARANCES
If Not Using Mantel
Note: If using a mantel, proceed to If Using
Mantel. If not using a mantel, follow the infor-
mation below.
You must have noncombustible material(s)
above the fireplace opening. Noncombustible
materials (such as slate, marble, tile, etc.)
must be at least 1/2" thick. With sheet metal,
you must have noncombustible material be-
hind it. Noncombustible material must extend
at least 12" up (for all models). See Figure 5
for minimum clearances.
Heat Resistant
Material
(A)
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
Noncombustible
Material Distance (A)
Requirements for Safe
Installation
12" or more
Noncombustible mate-
rial OK.
Between 8"
and 12"
24" Models: Install fire-
place hood accessory
(GA6050 or GA6053, see
Accessories
, page 26).
18" Model: Noncombus-
tible material OK.
Less than 8"
Noncombustible material
must be extended to at
least 8". See
Between
8" and 12"
, above. If you
cannot extend material,
you must operate heater
with flue damper open and
damper clamp installed.