INSTALLATION
Continued
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up.
NPT tap must be upstream from heater (see
Figure 14).
IMPORTANT:
Install equipment shutoff valve
in an accessible location. The equipment
shutoff valve is for turning on or shutting off
the gas to the appliance.
Check your building codes for any special
requirements for locating equipment shutoff
valve to fireplaces.
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could
result in clogged heater valves.
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
We recommend that you install a sediment trap
in supply line as shown in Figure 14. Locate
sediment trap where it is within reach for
cleaning. Install in piping system between
fuel supply and heater. Locate sediment
trap where trapped matter is not likely to
freeze. A sediment trap traps moisture and
contaminants. This keeps them from going
into heater controls. If sediment trap is not
installed or is installed wrong, heater may
not run properly.
CAUTION: Avoid damage to
gas control. Hold gas fitting with
wrench when connecting it to
gas piping and/or fittings.
* Purchase the optional equipment shutoff
valve from your dealer.
** Minimum inlet pressure for purpose of input
adjustment.
Figure 14 - Gas Connection
Gas
Control
3” Minimum
Equipment Shutoff
Valve With 1/8"
NPT Tap*
Approved
Flexible
Gas Hose (if
allowed by
local codes)
PROPANE/LP
From External
Regulator (11"
W.C.** to 14" W.C.
Pressure)
NATURAL
From Gas Meter
(5" W.C.** to
10.5" W.C.
Pressure)
Cap Pipe Tee
Nipple Joint
Sediment Trap