www.fmiproducts.com
125326-01A
14
Figure 18 - Control Knob in the OFF
Position for Thermostat Models
Control
Knob
O
OT
Control
Knob
Note: If pilot goes out, repeat steps 4
through 7. Wait one (1) minute before light-
ing pilot
9. Turn control knob counterclockwise
to desired heating level. The main burner
should light.
10. To shut off burners only and leave pilot lit,
turn control knob clockwise
to the
PILOT position.
WARNING: Always operate
manual control heaters at the
locked positions. Operation
between these positions may
create a possible health hazard
if used in a poorly ventilated
room. Read owner’s manual for
complete instructions.
Figure 19 - Pilot (actual pilot may vary)
OPERATION
Continued
Thermocouple
Ignitor Electrode
Pilot Burner
TO TURN OFF GAS
TO APPLIANCE
1. Turn control knob clockwise
to the
OFF position.
2. Turn off all electric power to the appliance
if service is to be performed.
2. Close equipment shutoff valve (see Figure
15, page 13).
MANUAL LIGHTING
PROCEDURE
1. Remove front panel (see Figure 6, page 9).
2. Follow steps 1 through 5 under
Lighting
Instructions
, page 15.
3. With control knob pressed in, strike match.
Hold match to pilot until pilot lights.
4. Keep control knob pressed in for 30 sec
-
onds after lighting pilot. After 30 seconds,
release control knob. Now follow step 9
under
Lighting Instructions
, page 15.
5. Replace front panel.
THERMOSTAT CONTROL
OPERATION
Thermostat models only
The thermostatic control used on these
models differs from standard thermostats.
Standard thermostats simply turn on and off
the burner. The thermostat used on this heater
senses the room temperature. At times the
room may exceed the set temperature. If so,
the burner will shut off. The burner will cycle
back on when room temperature drops below
the set temperature. The control knob can be
set to any comfort level between 1 and 5. All
plaques will turn off and on.
Note: The thermostat sensing bulb mea-
sures the temperature of air near the heater
cabinet. This may not always agree with
room temperature (depending on housing
construction, installation location, room size,
open air temperatures, etc.) Frequent use of
your heater will let you determine your own
comfort levels.
Figure 17 - Control Knob in the OFF
Position for Manual Control Models
CAUTION: Do not try to ad-
just heating levels by using the
equipment shutoff valve.