www.fmiproducts.com
125325-01A
13
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
WARNING: Never use an
open flame to check for a leak.
Apply a noncorrosive leak detec
-
tion fluid to all joints. Bubbles
forming show a leak. Correct all
leaks at once.
CAUTION: For propane/LP
units, make sure external regula
-
tor has been installed between
propane/LP supply and heater.
See guidelines under
Connecting
to Gas Supply
, page 12.
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1. Disconnect appliance with its appliance
main gas valve (control valve) and equip-
ment shutoff valve from gas supply piping.
Pressures in excess of 1/2 psig will dam-
age heater regulator.
2. Cap off open end of gas pipe where equip-
ment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
4. Check all joints of gas supply piping system.
Apply a commercial leak detection solution
to all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff
valve to gas supply. Check reconnected
fittings for leaks.
Figure 14 - Gas Connection
Tee Pipe Cap
Joint Nipple
Tee Joint
Reducer
Bushing to
1/8" NPT
1/8" NPT
Plug Tap
Pressure
Regulator
Te
st
G
au
ge
C
on
ne
ct
io
n*
Heater
Cabinet
Sediment Trap
3"
Min.
Natural Gas
From Gas
Meter (7" W.C.
to 10.5" W.C.
Pressure)
Propane/LP
From External
Regulator
(11" W.C. to 14"
W.C. Pressure)
Regulator
Bracket
Ground
Joint
Union
3/8" NPT
Pipe
Nipple
Equipment
Shutoff
Valve*
Connection Using Flexline
3/8" NPT/ 1/2"
Flare 90° Elbow
Flexline
See
illustration
above for
detail
Refer to connector's
instructions
IMPORTANT:
Hold the pressure regulator
with wrench when connecting it to gas pip-
ing and/or fittings. Do not over tighten pipe
connection to regulator. The regulator body
could be damaged.
INSTALLATION
Continued
* An equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge
connection. Purchase the optional equipment
shutoff valve from your dealer.