View Operation Data Using the Web Tool
View Operation Data Using the Web Tool
Available
Information
Menus
The table shows the available information menus on the main (left) menu:
Function
Description/Sub menu
MAS network overview
Displays key data and alarm status from other MAS units
connected to the same network.
Quick overview
Indicates the status of all monitoring channels and present
measurement results.
Trend diagrams
Up to three monitored channels can be plotted and viewed
simultaneously in one chart.
Running statistics
Contains histograms, a list of recent start and stops and
trip meter data.
Active alarms
A list of channels, where the monitored quantity currently
exceeds an alarm limit.
Alarm and event log
Shows active, acknowledged and reset alarms and events.
Light blue list items link to a plot function where you can view
graphs of the data leading up to and before/after the alarm.
Monitoring channels
The monitoring channels currently available are between
the next two yellow lines of the main menu (Temp stator ph
1-3 to System power factor). There are separate pages for
each channel containing a chart showing logged data of
desired resolution, average values, min and max.
Analog output
Shows the present value of the 4-20 mA output.
Digital I/O ports
Shows the status of output relays and digital inputs Run
and Reset.
Pump info
Contains pump data plate info, service log (notes) and when
service will be prompted.
Data log
A function to download measured data for export.
View
Status and
Measurement
Results
Present status and measurement results are shown in the Quick overview window for a
quick analysis of the pump status.
Follow these steps to view status and measurement results:
1.
Click View – Quick overview.
Result:
Present status and measurement results are shown in the Quick overview
window. There are separate columns for max and min display values since the
latest reset.
116