General Data F 460 Ex and F 460 -1 Ex

 

 

 

Comply with the operating instructions of the pump.

 

 

 

Never store the motor in areas in which corrosive vapours exist.

  

 

 

 

Before inserting the electrical plug into the socket, ensure that the Start/Stop 

 

    switch is set to "0" (Stop).

 

 

 

Regularly check the motors according to the relevant national safety regulations and/or 

 

    rules for prevention of accidents.

Safety Instructions

 

 

 

Power supply must include a fault current breaker. 

 

  

Dirt accumulation, high humidity or material damage on the motor housing may lead to 

 

    dangerous current surges.

2

 

 

  The motors F 460 Ex and F 460-1 Ex are equipped with an integral overload cut-out switch.

 

    The motor is switched off automatically in case of overloading. After having cooled down, 

 

    the motor can be switched on again by actuating the Start/Stop switch.

 

 

 

  Make sure that the motor is secured against unintentional re-starting. 

 

    The pump is to be arranged in a way that no friction and impinge sparks may form.

Replacement of power supply cable

  

 

When replacing the power supply cable, only UL-listed cables and plugs may be used. 

 

    Cable type at least: SO/SOW 3X16 AWG / 600V.

 

  

 

If the power supply cable has been properly mounted, the insulation resistance must be 

 

    tested and must be higher than 2 M

.

 

 

  The resistance of ground wire must not exceed 100 m

Ω.

Testing / Repair

 

 

 

  

Repairs to explosion-proof motors should only be carried out by the manufacturer or 

 

    by an authorized repair shop.

F 460 Ex

F 460-1 Ex

Class

1

1

Group

C and D

C and D

RPM

8500

9500

Insulation Class

F

F

Phase

1

1

Max. Amb.

+40°C

+40°C

Temperature code

T4

T4

Duty

Cont.

Cont.

Code Letter

A

A

Volts

120

120

Hz

60

60

A

4 A

6,8

Input Power

0,63 HP / 0,46 kW

0,95 HP / 0,7 kW

Output Power

0,46 HP / 0,34 kW

0,72 HP / 0,53 kW