Installing the Multipoint with
Acquisition Unit Model 1941 or 1948
11
To hook up power to the Multipoint Power Recorder
X
Make the connection between the power source and the meter
power terminal strip on the Multipoint Base Unit.
For an AC connection,
connect line and neutral, ,
as labeled.
For a DC connection, connect the
positive and negative terminals, as
labeled.
For AC connections, a Clip-On Ferrite Bead (Reliable Power Meter
part number 13-043-0004) is included with the Multipoint Base Unit.
Use of this device will ensure compliance with the Class A limits for
radio noise emissions. It should be snapped over the Safety ground,
AC Neutral, and AC Line wires such that it encloses all three wires
simultaneously, and then positioned within 6 inches (150 mm) of the
power terminal strip on the Multipoint.
For an AC connection power must be provided through a dedicated
UL recognized circuit breaker. The wire used must be UL recognized
with a gauge to match the current rating of the dedicated circuit
breaker.
DC power is limited by an internal 5-ampere fuse that is not user
replaceable.
10 to 15 V DC return
No connection
+10 to 15 V DC
No connection
No connection
No connection
No connection
No connection
No connection
AC Neutral
AC Line
No connection