PQ400

PQ Window

Voltage/Current Measurement Feed-Through

Device for Electrical Enclosures

Instructions

PQ Window (the Product) is an accessory that mounts to the 
flat surface of a Type 12 electrical enclosure (derate to Type 1 
during measurements). When the Product is installed and signal 
feeds connected, you can safely perform voltage and current 
measurements from outside the enclosure. 
Standard 4 mm safety sockets on the front provides access 
to the three phases (A/L1, B/L2, C/L3), Neutral N, and Earth/
Ground for voltage measurements. The voltage outputs 
support instruments that are powered from the measurement 
line with a maximum power of 100 VA.
The Product supports current measurement with Fluke 
intelligent current sensors (iFlex1500-12, iFlex 3000-24, 
i40S-EL and i400S-EL). Go to 

www.fluke.com

 for a full list of 

compatible accessories. 
The 354x FC, 173x Power, and 174x Power Quality Loggers 
automatically read the sensor information, such as, the type, 
serial number, scale factor, and phase angle compensation. 
Use the optional adapter kit to connect instruments and 
current sensors that have BNC connectors.

Summary of Contents for PQ Window

Page 1: ...signal feeds connected you can safely perform voltage and current measurements from outside the enclosure Standard 4 mm safety sockets on the front provides access to the three phases A L1 B L2 C L3 N...

Page 2: ...visit http register fluke com To view print or download the latest manual supplement visit http us fluke com usen support manuals A Warning identifies conditions and procedures that are dangerous to t...

Page 3: ...y with local and national safety codes Use personal protective equipment approved rubber gloves face protection and flame resistant clothes to prevent shock and arc blast injury where hazardous live c...

Page 4: ...tandards Type 1 NEMA 250 Enclosure Type Enclosure suitable for indoor use under normal atmospheric conditions Protection against access to hazardous parts and ingress of solid foreign objects falling...

Page 5: ...Plate installed on PQ Window Frame with Cover Top Plate Decal Set Screws x6 flathead installed x6 panhead Cable Marker Set Current Test Leads x4 Note A single current test lead is available as an opti...

Page 6: ...alcohol and soft cloth Hex key bit 3 16 in not shown Pozidriv screwdriver 1 not shown Figure 2 Tool Requirements Accessories Fuse 2A I17XX BNC M2M Fluke 17XX 4 pin Male to BNC Male Cable 2 m 1x I17XX...

Page 7: ...t hole with the twist drill and use a step drill bit to enlarge the 6 mm 0 2 in pilot hole to 20 mm 0 8 in Or drill a 10 mm 0 4 in pilot hole and then enlarge the hole to 22 5 mm 0 875 in with a Punch...

Page 8: ...gh Box from the rear to the front plate Fasten the front plate with the 6 panhead screws 5 If the space for the standard configuration is too small remove the top plate and rotate in 90 increments to...

Page 9: ...rrule for stranded wires 4 Push the wire into the circular opening of the terminal Note To remove the wire push a 3 5 mm slotted screwdriver into the rectangular opening of the terminal and pull out t...

Page 10: ...ker 1 from the set see Figure 1 item on both ends of the cable for phase A L1 Continue with marker 2 for phase B L2 and marker 3 for phase C L3 and N and Earth Ground 5 Refer to local regulations to p...

Page 11: ...nt Category rating of the measurement instrument and accessories matches or exceeds the rating of the installation 3 Use the current test lead to connect the current measurement signal output of the P...

Page 12: ...ase Make sure the circuit is secure against reenergizing of the installation Use only specified replacement fuses Fuse Replacement To replace a fuse 1 De energize the installation 2 Loosen the four ca...

Page 13: ...x D 148 mm x 370 mm x 19 mm with cover opened Inside 140 mm x 158 mm x Di W x H x D Di 58 thickness of panel door in mm Supported Electrical Enclosures UL 50 NEMA Environmental Enclosure Type 1 Type...

Page 14: ...le batteries or damage from accident neglect misuse alteration contamination or abnormal conditions of operation or handling Resellers are not authorized to extend any other warranty on Fluke s behalf...

Page 15: ...reserved x Manual Title PQ400 Instructions Part Number 4954885 Supplement Issue 1 Print Date October 2018 Issue Date 3 19 Revision Date 1 2 19 Page Count 1 This supplement contains information necessa...

Page 16: ...e wire gauge used for the voltage inputs to the Product On the 13th page under Environment replace the Humidity with Humidity 10 to 90 non condensing in dependency of temperature according to IEC 6072...