Terminal 15-16; external STOP:
With this function, the batch controller can be interrupted or cancelled with an external switch.
The input must be switched once for interruption or switch twice for cancellation with a potential free
contact to the GND-terminal number 15 for at least 0.3 seconds.
Fig. 22: Terminal connections - External stop (typical)
Terminal 26-31: type CB / CH / CI / CT - communication RS232 / RS485 / TTL (option)
For connections, refer to figure: Overview of terminal connectors - Standard configuration and options
Full serial communications and computer control in accordance with RS232 (length of cable max. 15
meters) or RS485 (length of cable max. 1200 meters) is possible.
When using the RS232 communication option, terminal 27 is used for supplying the interface.
Please connect the DTR (or the RTS) signal of the interface to this terminal and set it active (+12V).
If no active signal is available it is possible to connect a separate supply between terminals
26 and 27 with a voltage between 8V and 24V.
Terminal GND - 01: type ZB backlight (option):
If the unit is supplied with a power supply:
type PD, PF or PM, the backlight supply is integrated.
type PX, use the terminals 00 and 01 to supply the backlight.
The backlight intensity is set in the setup menu: Display.