HF124PEN_v0501_04
Page 26
4.4.3. TERMINAL
CONNECTORS
The following terminal connectors are available:
15
16
SIGNAL
SAFETY
INPUT
7
8
I
GND
1
N
L1
2
I
9
10
SIGNAL
11
+
12
6
5
R1
R1
14
13
SIGNAL
+
3
4
R2
R2
POWER SUPPLY
TYPE PD / PF / PM
ANALOG
OUTPUT TYPE
AA / AB
AI / AP / AU
POWER SUPPLY
TYPE PX
INPUT A:
SENSOR SIGNAL
TYPE P:
PULSE INPUT
LO ALARM
OUTPUT R1
TYPE
OA/ OT / OR
HI ALARM
OUTPUT R2
TYPE
OA/ OT / OR
INPUT B:
SENSOR SIGNAL
TYPE P:
PULSE INPUT
Fig. 10: Overview of terminal connectors standard configuration F124-P and options.
REMARKS: TERMINAL CONNECTORS:
Terminal GND- 01- 02: Power Supply - only available with type PD / PF or PM:
T
YPE
SENSOR SUPPLY
T
erminal
bac
kli
gh
t
T
YPE
AA
T
YPE
AU
Type
O
A
Type
O
R
GND
01
02
PD
8-24V AC
8,2 / 12 / 24V max. 50mA
AC AC
◊
◊
◊
◊
PD
8-30V DC
8,2 / 12 / 24V max. 50mA
L-
L+
◊
◊
◊
◊
PF
24V AC
±
15%
8,2 / 12 / 24V max. 400mA
AC AC
◊
◊
◊
◊
PF
24V DC
±
15%
8,2 / 12 / 24V max. 400mA
L-
L+
◊
◊
◊
◊
PM
115-230V AC
±
15% 8,2 / 12 / 24V max. 400mA
EARTH
AC
AC
◊
◊
◊
◊
◊
Note PD
do not use a AC autotransformer (Spartrafo) without a galvanic isolation.
Note PF / PM
The total consumption of the sensors and outputs may not exceed 400mA@24V
◊
=option
Note: for power supply type PX: please read Terminal 07-08 !