Fluidwell F124-P Operation Manual Download Page 1

 

 

 

F124-P 

Ratio controller 

 

 

 

 
Signal input flowmeter: pulse, Namur and coil. 

Control output: (0)4-20mA/ 0-10V. 

Alarm outputs: high / low ratio alarm. 

Options: Intrinsically Safe, Modbus communication and backlight. 

 

   

F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries

 

Summary of Contents for F124-P

Page 1: ...pulse Namur and coil Control output 0 4 20mA 0 10V Alarm outputs high low ratio alarm Options Intrinsically Safe Modbus communication and backlight F Series Field mounted indicators for safe and hazar...

Page 2: ...of according to local regulations regarding waste electronic equipment If a battery is present in this product it should be disposed of separately The separate collection and recycling of your waste e...

Page 3: ...ocedures which if not performed correctly may lead to personal injury a safety hazard or damage of the F124 P or connected instruments A caution indicates actions or procedures which if not performed...

Page 4: ...rm 17 6 Power management 17 7 Flowmeter 18 8 Analog output 19 9 Communication optional 20 A Others 20 4 Installation 21 4 1 General directions 21 4 2 Installation surrounding conditions 21 4 3 Dimensi...

Page 5: ...transmitting possibilities with communication option Flowmeter input This manual describes the unit with a pulse type input from the flowmeter P version Other versions are available to process 0 4 20...

Page 6: ...or a drained battery To extend the battery life time option please make use of the power management functions as described in chapter 3 2 3 Display information The unit has a large transflective LCD...

Page 7: ...is instruction is meant for users operators 2 2 CONTROL PANEL The following keys are available Fig 2 Control Panel Functions of the keys This key is used to program and save new values or settings and...

Page 8: ...y the control method produces stable control but react not as quick as a normal PI controller Selection and programming Operation mode By pressing the PROG button Control is displayed and the followin...

Page 9: ...y to display the actual flowrate A Flowrate B is selected by pressing the SELECT button Selection and programming the ratio alarm values Note This function might not be accessible or visible due to a...

Page 10: ...y MUST be replaced shortly after Only original batteries supplied by the manufacturer may be used else the guarantee and liability will be terminated The remaining lifetime after the first moment of i...

Page 11: ...re to be observed Ensure that the measuring system is correctly wired up according to the wiring diagrams The housing may only be opened by trained personnel Take careful notice of the Safety rules in...

Page 12: ...with Each function has a unique number which is displayed below the word SETUP at the bottom of the display The number is a combination of two figures The first figure indicates the function group an...

Page 13: ...se sign or decrease sign will be displayed while you are programming When data is altered but ENTER is not pressed then the alteration can still be cancelled by waiting for 20 seconds or by pressing E...

Page 14: ...P Continue Hand Safety 5 ALARM 51 ALARMSET operate setup hidden disable 52 FLOWZERO default no relays ignore 53 RATIO ALARM LO Measure 0 0 100 0 54 RATIO ALARM HI Measure 0 0 100 0 55 DELAY RATIO LO 0...

Page 15: ...tioning of the system will be Example 1 Calculating the K factor Let us assume that the flowmeter generates 2 4813 pulses per liter and the selected unit is cubic meters m3 A cubic meter consists of 1...

Page 16: ...l point The following can be selected 00000 1111 1 2222 22 SV MIN RATIO LIMIT LO SETPOINT 32 This setting determines lowest allowed set point for the ratio mode 0 0 100 0 usually 0 SV MAX RATIO LIMIT...

Page 17: ...time than an alarm will be generated DELAY TIME ALARM RATIO HIGH 56 An alarm generated by SETUP 34 high can be ignored during X time period If the actual ratio is still incorrect after this delay time...

Page 18: ...PE OF SIGNAL EXPLANATION RESISTANCE FREQ MV REMARK NPN NPN input 100K pull up 6 kHz open collector NPN LP NPN input with low pass filter 100K pull up 2 2 kHz open collector less sensitive REED Reed sw...

Page 19: ...ut value as tuned with setting 84 85 Example 50 means that the safety output will be 12mA for example TUNE MIN 4MA 84 The initial minimum analog output value is 0 4mA or 0V However this value might di...

Page 20: ...e F124 P Your supplier will ask for this information in the case of a serious breakdown or to assess the suitability of your model for upgrade considerations VERSION SOFTWARE A2 For support and mainte...

Page 21: ...contact is no longer assured when the housing cover is removed or the panel cabinet has been opened danger from electrical shock The housing may only be opened by trained personnel Take careful notice...

Page 22: ...mm 30mm 22 5mm M20 x 1 5 M16 x 1 5 M16 x 1 5 30mm 30mm 22 50mm M20 x 1 5 22 5mm M20 x 1 5 M20 x 1 5 25mm 25mm 22 5mm 1 2 NPT 0 9 3x 1 2 NPT 0 12 0 12 0 9 HA HM HN HO HP HT HU 6 x M12 12mm 12mm 24mm 24...

Page 23: ...box flat bottom HE HF HG HH D 12mm 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 22 5mm 30mm 30mm D 16mm D 20mm 0 9 D 22mm 0 866 22 5mm 25mm 25mm D 20mm D 20mm D 16mm HC 75 mm 2 95 118 mm 4 65 104 mm 4 09...

Page 24: ...ue to impact or friction sparks between the enclosure and iron steel is excluded Do ground the aluminum enclosure properly as indicated if the F124 P has been supplied with the 115 230V AC power suppl...

Page 25: ...24V and PF PM max 400mA 24V The voltage is selected with the three switches inside the enclosure Warning be sure that all the leads to the terminals are disconnected from the unit when the internal pl...

Page 26: ...nectors standard configuration F124 P and options REMARKS TERMINAL CONNECTORS Terminal GND 01 02 Power Supply only available with type PD PF or PM TYPE SENSOR SUPPLY Terminal backlight T YPE AA T YPE...

Page 27: ...tion of this output is set Type OA An active 24V DC signal output is available with this option Max driving capacity 50mA 24V per output Requires power supply type PD PF PM Type OR A mechanical relay...

Page 28: ...loop Do connect the to terminal 7 and the to terminal 8 When power is applied to these terminals the optional internal battery will be disabled enabled automatically to extend the battery life time O...

Page 29: ...I An isolated passive 4 20mA signal control output is available with this option Max driving capacity 1000 Ohm 30VDC This option can be used with a battery powered unit but the life time of the batter...

Page 30: ...earthed at the sensor itself The maximum input frequency is approximately 10 kHz depending on the type of signal The input signal type has to be selected with the correct SETUP function read par 3 2...

Page 31: ...2V is offered on terminal 11 which has to be switched by the sensor to terminal 10 SIGNAL For a reliable pulse detection the pulse amplitude has to go above 1 2V Signal setting PNP LP employs a low pa...

Page 32: ...from the reed switch it is advised to select REED LP low pass filter read par 3 2 3 NAMUR signal The F124 P is suitable for flowmeters with an Namur signal The standard F124 P is not able to power the...

Page 33: ...ter type as describer for flowmeter A The 9 10 11 do correspond with the terminals 12 13 14 Terminal 15 16 safety mode With this function the controller can be switched to a safety mode by making this...

Page 34: ...Terminal 26 31 backlight type ZB option Note if the unit is supplied with a power supply type PD PF or PM the backlight supply is integrated so the text following is not applicable To power the backl...

Page 35: ...ns and precautionary measures in the front of this manual Safety Instructions When two or more active intrinsically safe circuits are connected to the indicator in order to prevent voltage and or curr...

Page 36: ...tion PC or the external supply connected to terminals 0 and 1 option PD or the circuit supply connected to terminals 7 and 8 option AP The maximum values for any of those circuits are those as defined...

Page 37: ...trinsically Safe power supply and sensor supply Terminal GND 01 and 11 TYPE SENSOR SUPPLY Terminal GND 01 02 PD Input voltage 8 30V DC 3 2 8 1V L L internally linked with terminal 01 Terminal 02 this...

Page 38: ...10 11 12 14 13 Common ground Common ground Signal Signal Supply Circuit depends on type of signal Supply Circuit depends on type of signal Flowmeter input type P pulse Flowmeter input type P pulse Ci...

Page 39: ...nputl Ci is negligibly small 15 16 Common ground 3 2V low pass filter 1M e g sounder e g sounder 9 10 11 12 14 13 Common ground Common ground Signal Signal Supply Circuit depends on type of signal Sup...

Page 40: ...cated Ex label are certified for replacement and use in hazardous areas Batteries for use in safe areas have no Ex label DO NOT EXCHANGE Using the wrong type of battery can pose a SERIOUS RISK For use...

Page 41: ...on will occur for example by placing dry silica gel sachet in the casing just before closing it Furthermore it is required to replace or dry the silica gel periodically as advised by the silica gel su...

Page 42: ...s Type HD Type HE Type HF Type HG Type HJ Type HH Type HK ABS enclosure Type HS Dimensions 130 x 120 x 75mm 5 10 x 4 72 x 2 95 LxHxD IP67 NEMA4X Drilling 2x PG9 1x M20 Drilling 2x M16 1x M20 Drilling...

Page 43: ...Ga Ex ia IIIC T100 C Da IP6x Explosion proof Type XD XF ATEX approval ref EX II 2 GD EEx d IIB T5 Weight appr 15kg Dimensions of enclosure 350 x 250 x 200mm 13 7 x 9 9 x 7 9 LxHxD Environment Electro...

Page 44: ...seconds Function Two outputs high and low ratio Type OA Active 24V DC transistor output max 50mA per output requires type AA PD PF or PM Type OR Isolated mechanic relay output max switch power 230V A...

Page 45: ...ll almost certainly be handled internally and if all mentioned values still appear correct no intervention by the operator is needed If the alarm occurs more often or stays active for a longer time pl...

Page 46: ...e unit 15 Flowrate indication 9 hand mode 8 high limit 16 High limit 19 Installation 21 Integration time IT 16 Intrinsic safety 35 Intrinsically Safe options 37 IP classification 21 keys 7 low limit 1...

Page 47: ...F124 P and options 26 Fig 11 Overview terminal connectors communication option 34 Fig 12 Overview terminal connectors backlight option 34 Fig 13 Overview terminal connectors XI Intrinsically Safe app...

Page 48: ...71 signal A coil lo 72 signal B coil lo 8 ANALOG OUTPUT 81 CO minimum low limit_ 0 0 82 CO maximum high limit 100 0 83 CO Safety mode 0 0 84 tune min 0V 0160 85 tune max 10V 6656 9 COMMUNICATION 91 b...

Reviews: