E126-P-EG
User Manual
FW_E126-P-EG_M_v0301-01_EN
Page 29
5.5.7
MENU 6: PRESSURE
A “fixed” line pressure value can be used for the calculations:
Enter the fixed line pressure for offset (
6.3: PRESSURE > OFFSET
) and set the span to zero
(
6.2: PRESSURE > SPAN
).
When no pressure sensor is connected, manually calibrate the low input value at
6.5: PRESSURE >
CALIB-LOW
to remove the range error alarm.
6
PRESSURE
6.1 UNIT
Programs the displayed unit of measurement for pressure. This setting
does not influence the actual calculations.
6.2 SPAN
Determines the measurement range of the (0)4-20 mA pressure sensor
according to the selected measurement unit.
Example
:
Calculating the span for pressure.
The sensor generates:
●
the minimum signal (4 mA) at a pressure of 2.5 bar.
●
the maximum signal (20 mA) at a pressure of 50 bar.
Therefore, the span should be set at (50 - 2.5 =) 47.5 bar.
6.3 OFFSET
Calculations are based on absolute pressures.
The flow computer must know the measured pressure at minimum signal. In
the above example 2.500 bar must be entered.
When using a gauge type pressure indicator, enter an offset to compensate
for environmental pressure (for example, air pressure, 1.013 bar).
6.4 FILTER
Stabilizes the pressure reading.
This digital filter setting produces a more stable but less actual reading.
The filter principal is based on three input values: the filter level (01-99), the
last calculated pressure, and the last average value. The higher the filter
level, the longer the response time of a changed value. Use trial and error
to find the best setting for your application.
RESPONSE TIME ON STEP CHANGE OF INPUT VALUE (IN % OF END VALUE)
Filter value
50%
75%
90%
99%
01
filter disabled
filter disabled
filter disabled
filter disabled
10
7 sec
14 sec
22 sec
44 sec
20
14 sec
28 sec
45 sec
90 sec
30
21 sec
41 sec
68 sec
136 sec
50
35 sec
69 sec
114 sec
228 sec
75
52 sec
104 sec
172 sec
344 sec
99
69 sec
137 sec
227 sec
454 sec
6.5 CALIB-LOW
Calibrates the input value for (0)4 mA. This setting is used because the
signal from the pressure sensor might not be exactly 4.0 mA (or 0.0 mA) at
minimum pressure. This function measures the real output value at
minimum pressure.
Make sure the offered signal is correct before calibration takes place
as this has a major effect on the accuracy of the system.
After pressing PROG, three settings can be selected:
●
CALIB: Calibrates the input with the actual (0)4 mA value. After pressing
enter, CAL SET is displayed as soon as calibration is completed. From
that moment, the analog value must be more than the calibrated value
before the signal will be processed.
●
DEFAULT: Reinstalls the manufacture’s values.
●
CAL SET: Selects the last calibrated value.