User Manual
E115-P
Page 46
FW_E115-P_M_v0301-01_EN
Type OT
Two passive transistor outputs (D1 and D2) are available with a maximum pulse frequency of
500 Hz. Max. driving capacity 300 mA @50 VDC.
● Terminals R1 and R3 are common ground (GND) terminals.
● When retransmit mode is selected the minimum on and off-time is 50 μs.
R1
R2
+
1234567
1234567
R3
R4
+
D2
D1
1234567
1234567
Common system ground
N O
. .
N O
. .
MEM
Fig. 28:
Terminals R1-R4: Transistor outputs D1 – D2
Type OR
One mechanical normally open relay output is available with a maximum pulse frequency of 0.5 Hz.
Max. switch power 240 V 0.5 A per output. With the OR option:
● Use power supply terminals P5-P6.
● The required supply voltage is 24 – 27 VDC!
● Be sure that the output frequency does not exceed 0.5 Hz, else the relay life time and reliability
will be reduced significantly.
● The output functionality of digital output D5 and D6 correspond to the functionality of digital
outputs D1 and D2, respectively
● When retransmit mode is selected, the relays are not activated.
R8
R9
+
N O
. .
D6
R10
R11
+
N O
. .
D5
RSM
1234567
Max. 0,5Hz
1234567
Max. 0,5Hz
Fig. 29:
Terminals R8-R11: Mechanical relay outputs D5 – D6
6.4.10 TERMINALS S1-S3 SIGNAL A AND S4-S6 SIGNAL B: FLOWMETER INPUT
Three basic types of flowmeter signals can be connected to the unit: pulse, active pulse or sine-
wave (coil). The screen of the signal wire must be connected to the common ground terminal (unless
earthed at the sensor itself).
The sensor output should match with the selected flowmeter setting assigned in
SETUP