MODBUS-REGISTERS: MODBUS COMMUNICATION
[d] 149
[h] 0x095
40150
index use
1
R/W
uint16 0=static
1=auto
increment
2=auto
decrement
[d] 25
[h] 0x019
40026
reboot
1
R/W
uint16 Returns 0 on read
Write 0xA50F for unit restart
Write 0x5AF0 for factory settings
MODBUS-REGISTERS: DATALOGGING (WITH TYPE ZL)
PDU
ADDRESS
HOLDING
REGISTER
VARIABLE
NO. OF
REG’S
R/W
TYPE VALUES / REPRESENTATION / REMARKS
[d] 576
[h] 0x240
40577
log interval
1
R/W
uint16 0=off
1=1min
2=5min
3=10min
4=15min
5=30min
6=1hr
7=2hrs
8=4hrs
9=6hrs
10=8hrs
[d] 577
[h] 0x241
40578
daily log
1
R/W
uint16 0=off
1=single
2=dual
[d] 578
[h] 0x242
40579
daily1
1
R/W
uint16 00:00…23:59
Representation: hh:mm
Stored decimal: 23:59 = 2359d = 0x0937
[d] 580
[h] 0x244
40581
daily2
1
R/W
uint16 00:00…23:59
Representation: hh:mm
Stored decimal: 23:59 = 2359d = 0x0937
[d] 176
[h] 0x0B0
40177
local time
2
R/W
uint32 00:00:00…23:59:59
Representation: hh:mm:ss
Stored decimal: 23:59:59 = 235959d = 0x0003.99B7
[d] 179
[h] 0x0B3
40180
date
2
R/W
uint32 2000-01-01…2099-12-31
Representation: yyyy-mm-dd
Stored decimal: 99-12-31 = 991231d = 0x000F.1FFF
MODBUS-REGISTERS: OTHERS
PDU
ADDRESS
HOLDING
REGISTER
VARIABLE
NO. OF
REG’S
R/W
TYPE VALUES / REPRESENTATION / REMARKS
[d] 160
[h] 0x0A0
40161
model number
1
R
uint16 0…9999
[d] 173
[h] 0x0AD
40174
model suffix
1
R
char
Representation: ASCII character
[d] 162
[h] 0x0A2
40163
firmware
version
2
R
uint32 0…999999
Representation: xx.xx.xx
[d] 165
[h] 0x0A5
40166
serial number
2
R
uint32 0…9999999
Representation: xxxxxxx
[d] 176
[h] 0x0B0
40177
local time
2
R/W
uint32 00:00:00…23:59:59
Representation: hh:mm:ss
Stored decimal: 23:59:59 = 235959d = 0x0003.99B7
[d] 168
[h] 0x0A8
40169
password
1
R
uint16 0…9999
[d] 139
[h] 0x08B
40140
keyboard lock
1
R/W
uint16 0=disable
1=enable
[d] 170
[h] 0x0AA
40171
tag number
2
R/W
uint32 0…9999999
Representation: xxxxxxx