0000137242
Rev. 7.1
28
•
Menu index “3B2” CHLORINE/BROMINE FREQU OUT
The frequency output (Open collector circuit) can be used to control and guide the dosing of a remote
system in proportion to the Chlorine measurement.
•
Menu index “3B3” CHLORINE/BROMINE mA OUT
Note: The value set under the HOLD mA item is automatically generated by the instrument when a functional Hold
is present, for example due to a lack of water Flow Alarm or an enabled Voltage Input.
•
Menu index “3B4” CHLORINE ALARM
Note: The Holding Range and Holding Time items must be used together.
The indicated function controls the chemical measurement at a constant value for long periods of time.
This alarm can help to prevent incorrect dosing as a result of damaged probes.
•
Menu index “3B5” Reference temperature for CHLORINE/BROMINE measurement
Select 18, 20 or 25°C as the reference temperature for the chlorine measurement.
•
Menu index “3B6” Compensation of chlorine/bromine based on conductivity of the water.
Select reference conductivity between Low less than 9 mS and High greater than 9 mS.
Item
Default Value
Range
FWM Standard:
SetPoint:
1.2 ppm
0-5 ppm(0-12ppm for Br)
Dose Type:
Low
High / Low
Pulses/minute:
20 pulses/minute
20-150 pulses/minute
Proportional Band:
0.6 ppm
0.3-3 ppm(0.1-7.2 ppm for Br)
Item
Default Value
Range
Standard Out mA:
Range 0/4-20mA:
4-20 mA
0-20 mA or 4-20 mA
Start (4): 0 pH
0 ppm
0-5ppm(0-12ppm for Br)
End (20): 14 pH
10 ppm
0-5ppm(0-12ppm for Br)
Hold Function mA
Value: 0/4 or 20 mA
0 mA
0-20 mA
Item
Default Value
Range
pH Alarms List
Alarm minimum:
0.5 ppm
0-5ppm(0-12ppm for Br)
Alarm Maximum:
1.8 ppm
0-5ppm(0-12ppm for Br)
OFA (Maximum dose timer):
Off
10-3600 Seconds
Holding range:
Off
0.2-3 ppm(0.1-7.2 ppm for Br)
Holding time:
Off
10-3600 Seconds
Level Alarm: System stop or
alarm display
Disabled
Enabled/Disabled
3B2 CHLORINE
/BROMINE
FREQU OUT
SET POINT: 1.20ppm
DOSE TYPE LOW
PULSE: 20/min
↓↓↓↓
3B2 CHLORINE
/BROMINE
FREQU OUT
DOSE TYPE: LOW
↑↑↑↑
PULSE: 20/min
PROP BAND: 0.60ppm
3B3 CHLORINE
/BROMINE
mA OUT
RANGE: 4-20 mA
START( 4): 0.00ppm
END (20): 5.00ppm
↓↓↓↓
3A3 CHLORINE
/BROMINE
mA OUT
START( 4): 0.00ppm
↑↑↑↑
END (20): 5.00ppm
HOLD mA: 0.00mA
3B4 ALARMS
MIN VAL.: 0.50ppm
MAX VAL.: 1.80pppm
OFA: OFF
↓↓↓↓
3B4 ALARMS
HOLDING RANGE: OFF
↑↑↑↑
HOLDING TIME: OFF
LEV ALARM: DISABLED
Summary of Contents for 66170
Page 2: ...0000137242 Rev 7 1...
Page 270: ...0000137242 Rev 7 1 9...
Page 336: ...0000137242 7 1 1 PH REDOX 1 2 3 4 5...
Page 337: ...0000137242 7 1 2 1 1 1 1 2 1 3 85 265Vac 50 60 1 4...
Page 338: ...0000137242 7 1 3 IP65 0 C 40 C 25 C 65 C 00 95 2 15 100 240Vac 50 60 15 Switching...
Page 340: ...0000137242 7 1 5 15 2 2 2 2 1 100Vac 240Vac 50 60 2 2 2 10 230 230...
Page 348: ...0000137242 7 1 13 C R4...
Page 360: ...0000137242 7 1 25 L L m3 Gal o 3F NTU 3F1 ON OFF 3F2 3F3 3F4...
Page 372: ...0000137242 7 1 37 5 o o o o o o o o o o 500 o o Vdc In o o...