FlowLine Thermo-Flo LC80 Series Manual Download Page 13

Rev

 

B

 

MN301530

 

13

 

of

 

14

 

APPENDIX

 

Step

 

Nine

 

Relay

 

Latch

 

Logic

 

(Relay

 

2,

 

LC82

 

Series

 

only):

   

This

 

relay

 

is

 

primarily

 

a

 

flow/no

flow

 

relay.

  

However,

 

when

 

used

 

as

 

a

 

level

 

relay,

 

it

 

can

 

either

 

be

 

an

 

independent

 

relay

 

(high

 

or

 

low

 

level

 

alarm)

 

or

 

a

 

latching

 

relay

 

(automatic

 

fill

 

or

 

empty)

 

with

 

latch

 

ON.

  

With

 

Latch

 

OFF,

 

the

 

relay

 

will

 

only

 

respond

 

to

 

the

 

Input

 

2A.

   

Input

 

2B

 

will

 

be

 

ignored.

   

This

 

configuration

 

is

 

ideal

 

for

 

alarming,

 

such

 

as

 

flow,

 

no

flow,

 

leak

 

detection,

 

high

 

level

 

or

 

low

 

level.

 

When

 

the

 

Latch

 

switch

 

is

 

ON,

 

Relay

 

2

 

requires

 

that

 

both

 

Inputs

 

2A

 

and

 

2B

 

to

 

be

 

in

 

the

 

same

 

state

 

before

 

the

 

relay

 

will

 

switch.

   

In

 

an

 

auto

 

fill

 

application,

 

when

 

the

 

bottom

 

switch

 

is

 

dry

 

(top

 

switch

 

is

 

also

 

dry)

 

the

 

relay

 

will

 

energize.

  

The

 

relay

 

will

 

remain

 

in

 

an

 

energized

 

state

 

until

 

the

 

top

 

switch

 

becomes

 

wet

 

(bottom

 

switch

 

is

 

also

 

wet).

  

At

 

this

 

point,

 

the

 

relay

 

will

 

de

energize

 

and

 

remain

 

de

energized

 

until

 

the

 

bottom

 

switch

 

becomes

 

dry

 

again.

   

The

 

same

 

logic

 

applies

 

for

 

auto

 

empty

 

applications.

  

The

 

only

 

change

 

is

 

that

 

the

 

relay

 

will

 

energize

 

when

 

the

 

top

 

is

 

wet

 

(bottom

 

is

 

also

 

wet)

 

and

 

de

energize

 

when

 

the

 

bottom

 

is

 

dry

 

(top

 

is

 

also

 

dry).

  

In

 

both

 

scenarios,

 

when

 

the

 

level

 

is

 

between

 

the

 

two

 

sensors,

 

the

 

relay

 

will

 

not

 

change

 

state,

 

regardless

 

of

 

is

 

the

 

liquid

 

is

 

rising

 

or

 

falling.

  

This

 

logic

 

is

 

ideal

 

for

 

the

 

controlling

 

of

 

liquid

 

between

 

to

 

unique/different

 

set

 

points.

   

The

 

differential

 

is

 

controlled

 

by

 

the

 

location

 

of

 

the

 

two

 

sensors.

 

Caution:

   

Some

 

sensors

 

may

 

have

 

their

 

own

 

inverting

 

capability

 

(wired

 

NO

 

or

 

NC).

  

This

 

will

 

change

 

the

 

logic

 

of

 

the

 

invert

 

switch.

 

Check

 

your

 

system

 

design.

 

Invert

 

OFF

 

Latch

 

OFF

 

Input

 

2A

 

Input

 

2B

 

Relay

 

ON

 

OFF

 

No

 

Effect

 

No

 

Effect

 

ON

 

OFF

 

 

Invert

 

OFF

 

Latch

 

OFF

 

Input

 

2A

 

Input

 

2B

 

Relay

 

ON

 

OFF

 

No

 

Effect

 

No

 

Effect

 

OFF

 

ON

 

 

With

 

Latch

 

ON,

 

the

 

relay

 

will

 

actuate

 

when

 

Input

 

2A

 

and

 

Input

 

2B

 

are

 

in

 

the

 

same

 

condition.

  

The

 

relay

 

will

 

not

 

change

 

its

 

condition

 

until

 

both

 

inputs

 

reverse

 

their

 

state.

 

Invert

 

OFF

 

Latch

 

ON

 

Input

 

2A

 

Input

 

2B

 

Relay

 

ON

 

OFF

 

ON

 

OFF

 

ON

 

ON

 

OFF

 

OFF

 

ON

 

No

 

Change

 

No

 

Change

 

OFF

 

 

Invert

 

ON

 

Latch

 

ON

 

Input

 

2A

 

Input

 

2B

 

Relay

 

ON

 

OFF

 

ON

 

OFF

 

ON

 

ON

 

OFF

 

OFF

 

OFF

 

No

 

Change

 

No

 

Change

 

ON

 

 

 
 
 

 

Summary of Contents for Thermo-Flo LC80 Series

Page 1: ...Rev B MN301530 1 of 14 Thermo Flo Remote Flow Controller LC80 LC82 Series Manual Flowline Inc 10500 Humbolt Street Los Alamitos CA 90720 Tel 562 598 3015 Fax 562 431 8507 www flowline com...

Page 2: ...to 60 second delay Easy setup with LED indicators for sensor s power and relay status 35mm DIN rail mount polypropylene enclosure with removable terminal strips Invert switch changes relay state from...

Page 3: ...tact delay 0 to 60 seconds Electronics temp F 40 to 158 C 40 to 70 Enclosure rating 35mm DIN EN 50 022 Enclosure material PP U L 94 VO Fail safety Power fail safe Classification General purpose Approv...

Page 4: ...mmended Wiring should be performed by qualified personnel in accordance with all applicable national state and local electrical codes Flammable or Explosive Applications The entire LC80 series remote...

Page 5: ...nt sensor technologies where possible While this manual offers some examples and suggestions to help explain the operation of FLOWLINE products such examples are for information only and are not inten...

Page 6: ...oad of not more than 10 amps for reactive loads the current must be derated or protection circuits used When the red LED is ON and the relay is in the energized state the NO terminal will be closed an...

Page 7: ...C will be used in different applications Remember that the normal state is when the relay coil is de energized and the Red relay LED is Off de energized Both terminals share the Common C terminal When...

Page 8: ...hite can also be wired to the flow controller See the illustration below to indicate wiring for your switch and the polarity of the switch output Note the Shield wire will be used only for long cable...

Page 9: ...whether the switch is in a Flow or No Flow state With the flow switch wired NC the Amber LED indicates No Flow and no LED indicates flow Wiring the switch NO reversing the Red and Black wires the Ambe...

Page 10: ...and the relay LED will be ON So for this wiring configuration Invert should be set to the ON position If the switch is wired NO the input LED and the relay LED will be ON simultaneously So for this w...

Page 11: ...le through the potentiometer If the LED is on slowly adjust the potentiometer counterclockwise with a small flat head screwdriver until the LED turns off The adjustment is a single turn 270 potentiome...

Page 12: ...hat relay click on and off as well as the relay LED The Flow or No Flow is not switching at the correct flow rate The flow switch may need to be adjusted Review the Flow Switch Calibration section on...

Page 13: ...r auto empty applications The only change is that the relay will energize when the top is wet bottom is also wet and de energize when the bottom is dry top is also dry In both scenarios when the level...

Page 14: ...ocedures outlined above 2 have been subjected to electrical mechanical or chemical damage due to improper accidental or negligent use 3 have been modified or altered 4 anyone other than service person...