FlowLine LP10 Series Owner'S Manual Download Page 5

Models LP10-___2 & LP10-___3 Only

Wiring direct to a load, NC operation (FET signal output)

Wiring direct to load, Normally Open operation:
LP10-___2 and LP10-___3 (FET outputs only):

This is the same as the wiring for Normally Closed operation, except the
polarity of the Red and Black connections to the sensor is reversed. The
other connections remain the same; the sensor and device power
supplies remain tied in the same polarity as before.
 This method will turn
the load on when the sensor is wet.

Red*

Black*

White

Load

*Reverse Red & 
Black wires for  NO 
(NC shown)

Shield

Ground

Controller Device

(relay, lamp, valve, etc.)

100 mA Maximum

12 - 36 VDC

Power Supply

(Sensor)

+

-

N-Channel

Models LP10-___2, LP10-___3 & LP10-___5 Only

Wiring to a Flowline Controller

WIRING II

Step Six

LP10-___2

LP10-___3

Step Seven

LC40 Series Controller (4 or 20 mA signal output)

+

R E L A Y   1

R E L A Y   2

P O W E R

I N V E R T

I N V E R T

D E L A Y

-

-

+

-

-

D E L A Y

ONOFF

L A T C H

I N P U T 1

I N P U T 2 A

I N P U T 2 B

Shld

Not Used - White

Red
Black

Not Used - Green*

(+)

(-)

INVER

T

 +/-

INPUT

  1

DELAY

AC

AC

GND

NC

C

NO

R

P

115 VAC
220 VAC

Shld - Not Used

Red

Green* - Not Used

White - Not Used

Blac

k

LC10 Series Controller (4 or 20 mA signal output)

WIRING

Red*

Black*

White

Load

*Reverse Red & 
Black wires for  NO 
(NC shown)

Shield

Ground

Controller Device

(relay, lamp, valve, etc.)

100 mA Maximum

12 - 36 VDC

Power Supply

(Sensor)

+

-

P-Channel

*Reverse Red & Black wires for NC (NO shown)

Controller Device

(relay, lamp, valve, etc.)

1A Maximum

12 - 36 VDC

Power Supply

(Sensor)

+

-

Red*

Black*

Green

Shield

Ground

LXXX-XXX5
Relay Output

LOAD

60 VAC/VDC

Maximum

Power Supply

+

-

White

Models LP10-___5 Only

Wiring direct to a load, NO operation (Relay signal output)

LP10-___5

Wiring direct to load, Normally Closed operation:
LP10-___5 (Relay outputs only):

This is the same as the wiring for Normally Open operation, except the
polarity of the Red and Black connections to the sensor is reversed. The
other connections remain the same; the sensor and device power
supplies remain tied in the same polarity as before.
 This method will turn
the load on when the sensor is wet.