DataLoop™ LI25 Level Controller
Instruction Manual
34
MN301034 rev D
RESET METER TO FACTORY DEFAULTS
When the parameters have been changed in a way that is difficult to determine
what’s happening, it might be better to start the setup process from the factory
defaults.
Instructions to load factory defaults:
1. Enter
the
Advanced
features menu by holding the
Menu
button for 5
seconds. Press
Up
arrow until info is shown.
2.
Press and hold
Right
arrow/Reset for five seconds, press
Enter/Ack
when display flashes reset.
Note: If
Enter/Ack
is not pressed within three seconds, display returns to
Information
menu.
3.
The meter goes through an initialization sequence (same as on power-up),
and loads the factory default settings.