MN301535 Rev A
3
|
Specifications / Dimensions
Step Two
SPECIFICATIONS:
Supply voltage:
120 / 240 VAC, 50 - 60 Hz.
Consumption:
5 Watts max.
Sensor inputs:
LC90: (1) level switch
LC92: (1, 2 or 3) level switches
Sensor supply:
13.5 VDC @ 27 mA per input
LED indication:
Sensor, relay & power status
Contact type:
LC90: (1) SPDT Relay
LC92: (2) SPDT Relays,
1
Latching
Contact rating:
250 VAC, 10A
Contact output:
Selectable NO or NC
Contact latch:
Select On/Off (LC92 only)
Contact delay:
0.15 to 60 seconds
Electronics temp.:
F: -40°to 140°
C: -40°to 60°
Enclosure rating:
35mm DIN (EN 50 022)
Enclosure material:
PP (U.L. 94 VO)
Classification: Associated
apparatus
Approvals:
CSA, LR 79326
Safety:
Class I, Groups A, B, C & D;
Class II, Groups E, F & G;
Class
III
Parameters:
Voc = 17.47 VDC;
Isc = 0.4597A;
Ca = 0.494µF;
La = 0.119 mH
DIMENSIONS:
Top View - All Models
Side View - All Models
CONTROLLER LABELS:
LC90 series faceplate:
1 sensor input, 1 relay
output.
LC92 series faceplate:
3 sensor input, 2 relay
outputs. One relay is latching and the other is a
single input relay.