FlowLine EchoPod UG06 Series Quick Start Manual Download Page 2

|

   2

 

QS310140 Rev A2 

WELCOME TO THE ECHOPOD

®

 QUICK START 

The EchoPod

®

 Quick Start provides basic mounting, setup and use instructions for getting the EchoPod

®

 

up and running quickly.  If you have a non-standard installation or setup requirement that is not 
addressed here, please refer to the EchoPod

®

 Manual or other support documentation located at 

flowline.com. 

 
WE DO YOUR LEVEL BEST 

 
Thank you for purchasing EchoPod

®

.  The sensor provides integrated LCD and three push-button 

configuration.  This quick start includes everything you’ll need to get the sensor up and running.   
 

COMPONENTS 

 
Depending on how the sensor part number that was shipped, EchoPod

®

 comes with a Viton

®

 gasket for 

installation and the Quick Start. 

 

 

 

EchoPod

®

 

UG06-0001-00 
UG06-0001-01 
UG06-0011-00 
UG06-0011-01 

EchoPod

®

 

UG12-0001-00 
UG12-0001-01 
UG12-0011-00 
UG12-0011-01 

USB

®

 Key Fob 

P/N: LI99-2001 

Viton

®

 gasket (2”) 

P/N:  200129 

G threaded version only 

Viton

®

 gasket (3”) 

P/N:  210157 

G threaded version only 

 

ENCLOSURE 

 
While the switch housing is liquid-resistant the EchoPod

®

 is not designed to be operational when immersed.  It 

should be mounted in such a way that the enclosure and transducer do not come into contact with the 
application media under normal operational conditions.   Before closing the enclosure, make sure that the 
enclosure gasket is properly seated, and that any conduit fittings, cable connectors or plugs are installed 
correctly and sealed.  

Note:

 If using the Flowline LM90-1001 (liquid tight fitting) on the ½” conduit, the cable 

minimum is 0.170” (4.3mm) and the maximum is 0.450” (11.4mm). 
 

CONFIGURATION 

 
When configuring EchoPod

®

, choose either the WebCal

®

 or Push Button method.  Either method will 

accomplish the goal of sensor configuration.  Changes to the configuration can be made using the alternative 
method.  When beginning with one method, it is recommended to complete the configuration before using the 
other method to make any adjustments. 
 

Note: When connecting the sensor to the WebCal

®

 Software, you must remove the display or the software will 

not connect.  Once completed, you can re-connect the display to the terminal. 

 

 

 

Summary of Contents for EchoPod UG06 Series

Page 1: ...umbolt Street Los Alamitos CA 90720 p 562 598 3015 f 562 431 8507 w flowline com QS310140 Rev A2 2017 Flowline Inc All Rights Reserved Made in USA UG06 UG12 Series Quick Start EchoPod Ultrasonic Liqui...

Page 2: ...ed version only ENCLOSURE While the switch housing is liquid resistant the EchoPod is not designed to be operational when immersed It should be mounted in such a way that the enclosure and transducer...

Page 3: ...al powe is 15 play and unp tor on the cir per terminals correspond Fob to Red to Black W to White G to Green inal screws w o your PC s U al a PC sof quires conne E w flowline co B storage spa ection t...

Page 4: ...the location of the sensor with respect to fittings risers dome tops and bottoms and identify where the measurements are taken from the sensor The HEIGHT and FILL H settings determine the 4 20mA span...

Page 5: ...Confirm units for use in Sensor Height and Fill Height settings Sensor Height Sets the location for 4mA It is based on the distance from the Empty level position bottom of tank to the Measurement loc...

Page 6: ...Cal software please refer to the WebCal manual located at flowline com webcal software Before configuration can be completed You must click the Write to Unit button to save the settings to the unit Th...

Page 7: ...E THE TANK Measuring the tank is one of the most important aspects in configuring the sensor When measuring the tank take into account the location of the sensor with respect to fittings risers dome t...

Page 8: ...o return to the TOP LEVEL MENU 9 Select RUN to return to Operational Mode Note The Height and Fill Height settings also determine the 4 to 20 mA current span The Height setting determines the 4mA posi...

Page 9: ...larger bulkhead fitting such as the LM52 3890 with a reducer bushing such as the LM52 2400 Use a flange with a 2 thread such as the LM52 2850 Weld a plastic 2 half coupling to the tank top Mounting i...

Page 10: ...he minimum diameter of the pipe is 3 minimum 4 for the UG12 series Larger diameter pipes can be used The pipe should be attached with a coupling or tank adapter and reducer bushing Avoid the use of mu...

Page 11: ...installation must have a redundant backup safety system installed Wiring should always be completed by a licensed electrician The sensor must be chemically compatible with the application Design a fa...

Page 12: ...2 have been subjected to electrical mechanical or chemical damage due to improper accidental or negligent use 3 have been modified or altered 4 anyone other than service personnel authorized by Flowl...

Reviews: