Step 3: Configure through WebCal 

These instructions will walk you through configuration of the EchoPod

® 

through 

WebCal. For more information, click the WebCal 

HELP

 button in the lower right 

corner or anywhere on the WebCal screen or refer to the EchoPod

® 

 manual       

found at 

www.flowline.com

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Using a Standpipe 

A standpipe may be used to dampen turbulence, separate surface foam from the 

point of measurement or  increase performance in heavy vapor. Select a 3” pipe 

 (a 2” pipe is usable, but the minimum)   and attach the EchoPod

®

 with a coupling  

and reducer bushing.  The pipe length should run the measurement span and the 

bottom of the pipe should remain submerged at all times to prevent foam from 

entering the pipe.  Cut the bottom end  of the pipe at 45° and drill a 1/4” pressure 
equalization hole high in the dead band. The pumps should not drive liquid past the 

open end of the standpipe which causes the liquid in the pipe to become turbulent.  

              

                              

 

 

 

 

 

 

WebCal Configuration Screen 

 

 

Mounting with a Standpipe 

Spec Tech Industrial Electric

               www.spectechind.com

888-773-2832

Spec Tech Industrial Electric

               www.spectechind.com

888-773-2832

Summary of Contents for EchoPod DX10 Series

Page 1: ...ligent use 3 have been modified or altered 4 anyone other than service personnel authorized by Flowline have attempted to repair 5 have been involved in accidents or natural disasters or 6 are damaged during return shipment to Flowline Flowline reserves the right to unilaterally waive this warranty and dispose of any product returned to Flowline where 1 there is evidence of a potentially hazardous...

Page 2: ...llation must have a redundant backup safety system installed Wiring should always be completed by a licensed electrician Supply voltage should never exceed 28 VDC Protect the sensor from excessive electrical spikes by isolating the power whenever possible The sensor materials must be chemically compatible with the liquids to be measured Design a fail safe system for possible sensor and or power fa...

Page 3: ...your EchoPod should be performed prior to mounting since it requires connection to your PC Step 1 Install the WebCal Software Download WebCal from www flowline com onto a PC with the following minimum specifications Windows 2000 XP Vista 7 10 MB storage space 256 MB RAM 1 USB 2 0 port Double click the WebCal icon to install before proceeding to Step 2 You must have an active Internet connection to...

Page 4: ...y vapor Select a 3 pipe a 2 pipe is usable but the minimum and attach the EchoPod with a coupling and reducer bushing The pipe length should run the measurement span and the bottom of the pipe should remain submerged at all times to prevent foam from entering the pipe Cut the bottom end of the pipe at 45 and drill a 1 4 pressure equalization hole high in the dead band The pumps should not drive li...

Page 5: ... vinyl tape to dampen vibrations For installations in open tanks and sumps 1 Use Flowline s LM50 1001 1 side mount bracket which includes a 2 x 1 thread reducer bushing Using the drop down menus on the left of the WebCal screen set the configuration for your application requirements When a selection does not apply to your application Not Applicable will appear in the drop down Make sure all drop d...

Page 6: ...guration file and click Save Config File Configuration is now complete Disconnect the USB Fob before continuing to the next step Mounting the EchoPod For updates to WebCal or to make sure you re using the most up to date version available click the Update tab on the top of the WebCal screen Write to Unit Send your configuration into EchoPod Wiring Diagram Open PDF wiring schematic of your configur...

Reviews: