FlowLine EchoPod DL24 Series Quick Start Manual Download Page 3

 

We do Your Level Best

 

We do Your Level Best

 

 

Wiring the EchoPod

®

 

After mounting the EchoPod

®

, make the necessary electrical connections.  A wiring 

diagram with specific recommendations for the sensor’s configuration can be printed 

from the WebCal program.  A typical  wiring diagram is shown on the next page. 

 

 

 

 

 

 

 

 

Red

 and 

Black

 leads are for connection to a 24 VDC power supply or to a 4-20 mA 

loop power source. The red and black wires can be extended more than 1000 feet 

using 22 gauge or larger wire, however do not extend the green and white wires. 

White

 and 

Green

 leads are reserved for use with WebCal and should not be 

connected during usage in the application.  These wires should not be connected to 

WebCal while power is supplied from any source other than the LI99 FOB. 

Never allow the white or green wires to touch any power supply. 

Blue

Orange

Yellow

 and 

Purple

 wires are the relay contacts (normally open) from 

each of the relays respectively. 

The 

Brown

 wire is the common for all of the relays.

 

 

 

 

 

Configuring the EchoPod

®

 

Configuration of your EchoPod

®

 should be performed prior to mounting, since it 

requires connection to your PC. 

 

Step 1: Install the WebCal Software 

Download WebCal from  

www.flowline.com

 onto a PC with the following minimum 

specifications: 

Windows

®

 2000/XP/Vista/7, 10 MB storage space, 256 MB RAM, 1 USB 2.0 port 

Double-click the WebCal icon to install before proceeding to Step 2. You must have 

an active Internet connection to install WebCal, as it will automatically verify driver 

updates. 

Step 2: Connect the USB Fob 

NOTE

: Do not connect the Fob until after you’ve installed WebCal. 

The EchoPod

®

 communicates to its configuration software through the USB Fob. 

Prior to connecting the Fob, ensure that all external power is disconnected from the 

EchoPod

®

 as power is provided through the PC’s USB 2.0 port. Do not use a cable 

connecting the EchoPod

®

 to the Fob any longer than 15 feet. 

1)  Connect the red, green, white, 

      and black wires from the 

EchoPod

®

 to the corresponding 

colored terminals on the Fob 
(as shown in the diagram). 

2)  Tighten the terminal screws with 

a slotted screwdriver. 

3)  Plug the Fob into your PC’s 

USB port. 

 

 

 

 

Spec Tech Industrial Electric

               www.spectechind.com

888-773-2832

Spec Tech Industrial Electric

               www.spectechind.com

888-773-2832

Summary of Contents for EchoPod DL24 Series

Page 1: ...ligent use 3 have been modified or altered 4 anyone other than service personnel authorized by Flowline have attempted to repair 5 have been involved in accidents or natural disasters or 6 are damaged during return shipment to Flowline Flowline reserves the right to unilaterally waive this warranty and dispose of any product returned to Flowline where 1 there is evidence of a potentially hazardous...

Page 2: ...stalled Wiring should always be completed by a licensed electrician Supply voltage should never exceed 28 VDC Always use stepper relays between the sensor and external loads For DC circuits use a catch diode such as 1N4148 as shown above Protect the sensor from excessive electrical spikes by isolating the power whenever possible The sensor materials must be chemically compatible with the liquids t...

Page 3: ...ration of your EchoPod should be performed prior to mounting since it requires connection to your PC Step 1 Install the WebCal Software Download WebCal from www flowline com onto a PC with the following minimum specifications Windows 2000 XP Vista 7 10 MB storage space 256 MB RAM 1 USB 2 0 port Double click the WebCal icon to install before proceeding to Step 2 You must have an active Internet con...

Page 4: ...y vapor Select a 3 pipe a 2 pipe is usable but the minimum and attach the EchoPod with a coupling and reducer bushing The pipe length should run the measurement span and the bottom of the pipe should remain submerged at all times to prevent foam from entering the pipe Cut the bottom end of the pipe at 45 and drill a 1 4 pressure equalization hole high in the dead band The pumps should not drive li...

Page 5: ...ot recommended 2 While installations directly into a 1 metal fitting are not recommended acceptable results may be obtained if the 1 fitting is a half coupling in form and the outer diameter of the coupler is tightly wrapped in vinyl tape to dampen vibrations For installations in open tanks and sumps 1 Use Flowline s LM50 1001 1 side mount bracket which includes a 2 x 1 thread reducer bushing Usin...

Page 6: ...ng the EchoPod For updates to WebCal or to make sure you re using the most up to date version available click the Update tab on the top of the WebCal screen Write to Unit Send your configuration into EchoPod Wiring Diagram Open PDF wiring schematic of your configuration Advanced Configure advanced settings Read the section below on advanced setting options Factory Config Return EchoPod to the orig...

Reviews: