FlowCon FN.0.2 Installation And Operation Instruction Download Page 2

FlowCon FN (digital)

Blue

Power 24V AC/DC

Ground/common

Grey

Brown

Open

FN.0.4 Actuator

2-Position, Normally Closed

Close

Blue

Power 24V AC/DC

Ground/common

Grey

Brown

Open

Stop

FN.0.4 Actuator

3-Point Floating, Normally Closed

Close

Blue

Yellow

Power 24V AC/DC

Ground/common

Green

Grey

Feedback signal

0(2)-10V DC

Feedback ground

0V DC

Input signal

0(2)-10V DC

<0.5mA

Brown

FN.0.2 / FN.1.2 Actuator

0(2)-10V modulating

FlowCon FN (analog)

Blue

Power 24V AC/DC

Ground/common

Grey

Brown

Open

FN.1.2 Actuator

2-Position, Normally Closed

Close

Yellow

Green

Feedback signal

0-10V DC

Feedback ground

0V DC

Wiring

Start-up Sequence

When power to the actuator is turned on, the 

actuator will automatically calibrate to determine 

closing point. Hereafter it will proceed to normal 

operation mode (according to control signal).

For the failsafe version (FN.1.2), capacitor 

charging will be prioritized (max. 120 sec de-

pending on capacitor energy level) during start-

up and re-powering. After completion of charging 

mode followed by calibration mode, the actuator 

will proceed to normal operation mode.

Auto Cycle Sequence

Auto Cycle can be activated during commission-

ing. It prevents the valve from jamming when the 

valve is not moved for a longer period of inactiv-

ity. By moving DIP switch #1 from OFF to ON, 

Auto Cycle is activated. Actuator will then per-

form 50% stroke cycle every 3 weeks if no stroke 

movement has occurred.

Electrical Override

By moving DIP switch #6 from OFF to ON, elec-

trical override is activated and the actuator will 

open valve fully. During electrical override the 

LED indicator will blink red and green. When DIP 

switch #6 is moved back to OFF, the actuator will 

re-calibrate and thereafter go into normal opera-

tion mode. Electrical override is performed with 

power supply on.

Failsafe Mode (FlowCon FN.1.2)

When power is lost, the actuator will go into fail-

safe mode after a few seconds, mandatory that 

capacitor charging and start-up sequence are 

completed. The actuator will perform failsafe 

action (open or close) and stay in failsafe final 

position until return of power. Upon power, the 

actuator remains in the final failsafe position until 

charging mode is reached (max. 60 sec). Here-

after the actuator will return to normal operation 

mode.

This paper is a supplement to the

 FlowCon General Instruction 

Latest release of any FlowCon material is available on

 

www.flowcon.com

FlowCon FN.0.2, FN.0.4 and FN.1.2 Actuators

1B95080 - 08/2019-2

Page 2 of 4

Summary of Contents for FN.0.2

Page 1: ...nt the actuator on the valve and finger tighten the connection union Do not use addi tional tools In case the actuator will have to be removed it is recommended to electrically open the actuator by activating DIP switch 6 for eas ier removal Hereafter finger loosen the connec tion union Again no need for additional tools Please make sure that the actuator is electrically opened before re fitting i...

Page 2: ...ed during commission ing It prevents the valve from jamming when the valve is not moved for a longer period of inactiv ity By moving DIP switch 1 from OFF to ON Auto Cycle is activated Actuator will then per form 50 stroke cycle every 3 weeks if no stroke movement has occurred Electrical Override By moving DIP switch 6 from OFF to ON elec trical override is activated and the actuator will open val...

Page 3: ...ectrical override ON Electrical override OFF 5 Failsafe open Failsafe close 4 Equal percentage Linear 3 Normally Open Normally Closed 2 Control signal 2 10V Control signal 0 10V 1 Auto cycle ON Auto cycle OFF 6 5 4 3 2 1 DIP Switch Settings The valve functions are set on DIP switches found under the connection cover PCB mounted electri cal components will not be directly exposed when DIP switches ...

Page 4: ...ing red green Failsafe mode n a n a OFF LED Status The LED indicator is visible through the dark colored transparent connection cover The LED indica tion will give the following statuses This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www flowcon com FlowCon FN 0 2 FN 0 4 and FN 1 2 Actuators 1B95080 08 2019 2 Page 4 of 4 FlowCon...