The actuator types
FlowCon FN.0.2, FN.0.4
and
FN.1.2
are electrical actuators. FN.0.2 is
24V modulating and FN.0.4 is 24V 3-point float-
ing and 2-position. FN.1.2 is 24V modulating and
2-position failsafe version.
Fitting and Re-fitting
Do not connect power to the actuator unless
the actuator is already fitted on the valve
and NEVER install the actuator in closed
position - this may damage the valve. Actu-
ator is supplied in open position to ensure
easy commissioning of the system.
Mount the actuator on the valve and finger
tighten the connection union. Do not use addi-
tional tools. In case the actuator will have to be
removed, it is recommended to electrically open
the actuator by activating DIP switch #6 for eas-
ier removal. Hereafter finger loosen the connec-
tion union. Again, no need for additional tools.
Please make sure that the actuator is electrically
opened, before re-fitting it on the valve.
Orientation
Upside-down installation is allowed (reduced IP
rating applies) along with the standard horizontal
and vertical installation.